Temperature Multi-Input Device
Troubleshooting
2
017-
05
35
6.8
Recommended Action for Field Diagnostics according to NE 107
Alarm Type
Diagnostic Event
Cause
Recommended
Action
Maintenance required Configuration error
Check blocks for
configuration errors.
Failed
Device failure
Body temperature
> +95
°
C
Send the device to
Fuchs for
repair.
Body temperature > -
50
°
C
NV storage
verification failed
NV storage write failed
Hardware error
detected
Channel 8 input failure Over-/underrange of
measured value.
Wiring error.
Check transducer
block for more details,
see manual.
Channel 7 input failure
Channel 6 input failure
Channel 5 input failure
Channel 4 input failure
Channel 3 input failure
Channel 2 input failure
Channel 1 input failure
Function check
Check
Check block modes
according to normal
mode.
Out of specification
Body temperature off
range.
Body temperature
> +90
°
C
Adjust ambient
temperature of
mounting locations
Body temperature < -
40
°
C