If the fail to start test is activated 

(using the option switches on the 

bottom of the controller), then the 

follow sequence is used each time 

a pump is called:
  1. When a pump is called a timer 

is started.

 2. After a start-up time has 

expired (set by switch 6), the 

pump running input is checked.  

If the pump is not running 

at the end of the time, then a 

pump fail to start condition is 

set and the pump is disabled. 

The pump will remain disabled 

until the reset button is pushed 

or until the external reset input 

is activated.

The controller has two relays for 

level alarm. Option switch 5 can 

be used to cause these relays to 

cycle on and off. This is useful to 

provide blinking on the external 

alarm lights.

There is one relay that can have 

either of two functions selected by 

option switch 4:
 1. If the horn option is selected, 

then this relay can be used to 

drive an external horn or bell.  

Whenever either a high or 

low alarm condition starts, the 

relay is activated (closed). If 

the alarm condition is cleared, 

then the relay is also cleared. 

If the reset button is pushed or 

the external reset/mute input is 

activated, then the horn relay 

is cleared. If the horn is muted, 

then it will not reactivate until 

the alarm condition is cleared 

and another starts.

 2. If the common alarm option 

is selected, then this relay will 

be activated when any of the 

following conditions exist:

   • High alarm
   • Low alarm
   • Pump temperature failure
   • Pump  disabled  by  fail  to     

  start test

This common alarm condition can 

be used to drive an alarm light, 

telephone dialer, or telemetry 

system.

There are six switches on the back 

of the controller which select 

several different options.
SW1 – When this switch is set, the 

fail to start test is enabled.
SW2 – When this switch is set, 

the temperature fail condition is 

latched up until reset.
SW3 – When this switch is set, the 

seal fail input is inverted (open is 

fault).
SW4 – When this switch is set, the 

aux relay is the common alarm.  If 

it is not set, then the aux relay is 

the horn output.
SW5 – When this switch is set, 

the low and high alarm relays will 

cycle, causing a lamp blink.

SW6 – When this switch is set, the 

time between pump starts and the 

delay for the fail to start test is 12 

seconds instead of 6 seconds.

There are seven fault lamps with 

corresponding driver outputs. They 

are used to display the following 

fault conditions:
  1. Floats out of order
  2. Pump 1 seal fail
  3. Pump 2 seal fail
  4. Pump 1 temperature fail
  5. Pump 2 temperature fail
  6. Pump 1 disabled
  7. Pump 2 disabled
Each of these has a corresponding 

relay drive output. These outputs 

are designed to drive the coil of 

a 12VDC relay external to the 

controller. A source of 12VDC 

is also provided. To use these 

outputs, one side of the relay coil 

is connected to 12VDC and the 

other coil connection is connected 

to the driver output.

Float and Sensor Inputs

There are five float inputs; two seal 

fail sensor inputs, two temperature 

fail inputs, and two disable inputs. 

They use current limiting resistors, 

filter capacitors and Zener diodes 

for transient protection. They also 

have both hardware and software 

filters on these inputs to improve 

immunity from noise. They have 

the following specifications: 

Fail To 

Start Test

Alarm Relay 

Outputs

Auxiliary 

Relay

Option 

Switches

Fault 

Outputs

Specifications

Summary of Contents for Hydromatic NOVUS 3000 Series

Page 1: ... provide this manual to the owner of the equip ment or to the responsible party who maintains the system NOVUS 3000 STANDARD ELECTRICAL CONTROLS INSTALLATION AND SERVICE MANUAL Item H 03 519 Part 5625 519 1 2012 Pentair Pump Group Inc 11 02 12 ...

Page 2: ...dicator lights and external relay drivers for the following conditions floats out of order seal fail for pumps 1 and 2 temperature fail for pumps 1 and 2 and pump disabled for pumps 1 and 2 Unpacking Panel Remove panel from carton When un pack ing unit check for con cealed damage Claims for damage must be made at the receiving end through the delivery carrier Dam age cannot be processed from the f...

Page 3: ...mally open float switches for level sensing When the tank is empty all of the floats are open The lowest float is the low alarm float If it is not used the low float input should be shorted with a jumper When the tank is empty the controller will be in the low alarm condition On rising water when the level is high enough to close the low float switch then the low alarm will go off As the level ris...

Page 4: ...is run ning Check for flow On three phase power check to see if each pump has prop er ro ta tion Wrong ro ta tion will give low flow 8 Check full load current with amp probe and compare it with the name plate rat ing On three phase pumps check all three phases On single phase pumps check black pump lead 9 Check operation of start relay if supplied on single phase panels per procedure in Item 7ofMa...

Page 5: ...es the resistance of the sensor In normal operation the seal fail condition is set if the resistance is less than 2000 ohms One of the option switches can be used to change this to set the alarm if the resistance is greater than 2000 ohms If a seal fail alarm is set then that pump is demoted to lag pump and its seal fail lamp and output are activated The seal fail does not disable the pump Each pu...

Page 6: ...er or telemetry system There are six switches on the back of the controller which select several different options SW1 When this switch is set the fail to start test is enabled SW2 When this switch is set the temperature fail condition is latched up until reset SW3 When this switch is set the seal fail input is inverted open is fault SW4 When this switch is set the aux relay is the common alarm If...

Page 7: ...inuous sink current 0 4 amps Maximum on resistance 2 ohms WARNING Before handling thesepumpsandcontrols always dis con nect the power first Do not smoke or use sparkable electrical devices or flames in a septic gas eous or possible septic sump 1 Pump does not run in Hand position a Check pump circuit breaker and control fuse for trip ping or blown condition b Check incoming power volt age and cont...

Page 8: ... miswired to ter mi nal block e Voltage and current unbalance Three phase only Voltage un bal ance on three phase power sources can cause motor current to become un bal anced and exces sive heating will re sult Trip ping of the over load protectors and premature motor failures can be expected if the current unbalance exceeds five percent Percent Maximum Current Current Difference from x 100 Unbala...

Page 9: ... lead c Set the amp meter scale to at least 2 times the pump motor full load current d Place the H O A switch in the Hand position to start the pump e The meter should read ap prox i mate ly 2 times full load current during starting f After the motor has started within one sec ond the cur rent should drop to a value much less than full load cur rent 5 Motor voltage check Typical Motor Voltage Comp...

Page 10: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 11: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 12: ...o and from the factory or an authorized Pentair Hydromatic service facility This limited warranty will not apply a to defects or malfunctions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such ser...

Reviews: