Pentair Hydromatic NOVUS 3000 Series Installation And Service Manual Download Page 4

4

Pump Start-Up:

Refer to pump Installation and 

Service Manual.

WARNING: Before handling 

these pumps and controls, 

always 

dis con nect 

the 

power first. Do not smoke or  

use sparkable electrical devices 

or flames in a septic (gaseous) or 

possible septic sump.
The maintenance schedule 

 

will vary with operating and 

 

environmental  con di tions. It will 

also vary with the specific type of 

control supplied. The list herein is 

a guide only.
 1. 

Exercise breaker through 

one cy cle. Be careful not to  

overexercise as the break 

er 

is not a switch ing device. 

Excessive operations tend 

 

to affect the trip curve of  

the breaker. 

 2. Check contactors and relays 

for excessive humming. This 

can be accomplished by 

 

turning pumps on and off 

in the Hand mode with the  

H-O-A switch.

  3.  Check  pump  run  light(s)  by       

run 

ning pump(s) in Hand 

 

mode. Check bulb(s) in any  

other light(s).

 4. With the power off, check  

con ti nu ity of all control fuses.

 5. Check voltage at primary 

 

and sec 

ond 

ary of control 

transformer.

 

6. 

Check the pump full 

 

load amps.

 7. For 1 phase panels with start 

circuit, about 5 seconds after 

the pump starts check the 

Black, and Red  pow 

er 

wires are con nect ed to pan el 

correct ly.

 3. WARNING! Live voltage can 

kill!  Check incoming power    

volt age to make sure that  

it is correct for panel and  

pump model.

 4. Energize control panel. (Turn 

on power to panel.)

 5. Check overload relay and 

 

verify reset mode (if overload 

is  sup plied).

 6. WARNING!  Live voltage 

can kill!  Check voltage to the  

panel and at secondary of  

control trans form er using a 

voltmeter. If no transformer is 

supplied, check volt age at the 

circuit breakers. 

 7. With H-O-A switch in hand, 

check dis charge to ver i fy the 

pump is run ning. Check for 

flow. On three phase power, 

check to see if each pump  

has  prop er  ro ta tion.  Wrong  

ro ta tion will give low flow.

 8. 

Check full load current 

 

with amp probe and compare 

it with the name plate rat ing. 

On three phase pumps, check  

all three phases. On single 

phase pumps, check black 

 

pump lead.

  9. Check operation of start relay, 

if supplied on single phase 

panels, per procedure in Item 

#7 of Maintenance Instructions.

 10. With H-O-A switch in Auto, 

check  float  op er a tion  and 

response to control panel to  

the float operation. For 

sequence of op er a tion, refer to 

design specification.

 11. Make sure H-O-A switch is left  

in  the  Auto  position  after     

start-up is completed.

voltage from terminal 1 to 

terminal 2 on the start relay 

to be sure that the relay has 

operated.  The voltage from 

terminal 1 to terminal 2 on 

the start relay must exceed 

10 VAC.  For some pumps 

the voltage may exceed 400 

VAC.  If after 5 seconds the 

voltage from terminal 1 to 

terminal 2 on the start relay 

does not exceed 10 VAC, stop 

the pump as the start capacitor 

may be damaged in about 15 

seconds.  

   If the start relay is not 

operating, check the pump and 

the system voltage to be sure 

that they match. Check the 

power wiring to ensure that the 

pump is connected properly.  

Start the pump once more and 

check that the voltage from 

the terminal for the black wire 

to the white wire is within 

system tolerance.  Call for 

help if you cannot resolve the 

problem.

 8. Check junction boxes for 

 

moisture. Moisture may 

 

cause chattering of relays 

 

and contactors. 

 9. Check for moisture inside 

 

control panel enclosure. 

Moisture can cause damage to 

electrical com ponents. Check 

door gasket for prop er seal.

 10. Check labels to verify they 

have not been damaged.

 11. Lubricate enclosure hinges.
 

12. Pull floats and check for 

 

proper operation and ensure 

there is no foreign buildup  

on them.

Pump

Maintenance

Summary of Contents for Hydromatic NOVUS 3000 Series

Page 1: ... provide this manual to the owner of the equip ment or to the responsible party who maintains the system NOVUS 3000 STANDARD ELECTRICAL CONTROLS INSTALLATION AND SERVICE MANUAL Item H 03 519 Part 5625 519 1 2012 Pentair Pump Group Inc 11 02 12 ...

Page 2: ...dicator lights and external relay drivers for the following conditions floats out of order seal fail for pumps 1 and 2 temperature fail for pumps 1 and 2 and pump disabled for pumps 1 and 2 Unpacking Panel Remove panel from carton When un pack ing unit check for con cealed damage Claims for damage must be made at the receiving end through the delivery carrier Dam age cannot be processed from the f...

Page 3: ...mally open float switches for level sensing When the tank is empty all of the floats are open The lowest float is the low alarm float If it is not used the low float input should be shorted with a jumper When the tank is empty the controller will be in the low alarm condition On rising water when the level is high enough to close the low float switch then the low alarm will go off As the level ris...

Page 4: ...is run ning Check for flow On three phase power check to see if each pump has prop er ro ta tion Wrong ro ta tion will give low flow 8 Check full load current with amp probe and compare it with the name plate rat ing On three phase pumps check all three phases On single phase pumps check black pump lead 9 Check operation of start relay if supplied on single phase panels per procedure in Item 7ofMa...

Page 5: ...es the resistance of the sensor In normal operation the seal fail condition is set if the resistance is less than 2000 ohms One of the option switches can be used to change this to set the alarm if the resistance is greater than 2000 ohms If a seal fail alarm is set then that pump is demoted to lag pump and its seal fail lamp and output are activated The seal fail does not disable the pump Each pu...

Page 6: ...er or telemetry system There are six switches on the back of the controller which select several different options SW1 When this switch is set the fail to start test is enabled SW2 When this switch is set the temperature fail condition is latched up until reset SW3 When this switch is set the seal fail input is inverted open is fault SW4 When this switch is set the aux relay is the common alarm If...

Page 7: ...inuous sink current 0 4 amps Maximum on resistance 2 ohms WARNING Before handling thesepumpsandcontrols always dis con nect the power first Do not smoke or use sparkable electrical devices or flames in a septic gas eous or possible septic sump 1 Pump does not run in Hand position a Check pump circuit breaker and control fuse for trip ping or blown condition b Check incoming power volt age and cont...

Page 8: ... miswired to ter mi nal block e Voltage and current unbalance Three phase only Voltage un bal ance on three phase power sources can cause motor current to become un bal anced and exces sive heating will re sult Trip ping of the over load protectors and premature motor failures can be expected if the current unbalance exceeds five percent Percent Maximum Current Current Difference from x 100 Unbala...

Page 9: ... lead c Set the amp meter scale to at least 2 times the pump motor full load current d Place the H O A switch in the Hand position to start the pump e The meter should read ap prox i mate ly 2 times full load current during starting f After the motor has started within one sec ond the cur rent should drop to a value much less than full load cur rent 5 Motor voltage check Typical Motor Voltage Comp...

Page 10: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 11: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 12: ...o and from the factory or an authorized Pentair Hydromatic service facility This limited warranty will not apply a to defects or malfunctions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such ser...

Reviews: