Pentair Hydromatic NOVUS 3000 Series Installation And Service Manual Download Page 5

5

Spare Parts List:

The following is a list of 

 

recommended spare parts. 

However, conditions of ser vice vary 

significantly and a general list may 

not in its entirety be applicable to a 

given installation. The user should 

ex 

er 

cise judgment in defining 

 

specific re 

quire 

ments based on 

 

this guide.
  1.  Fuses  for  control  transformer     

primary and secondary. 

 

(If required)

  2. Contactor.
 3. Bulbs for any light requiring  

a bulb.

  4. Control transformer.  

(If required)

  5. Alternator relay. (If required)

Optional: The LOW WATER / 

REDUNDANT OFF float should 

be installed just above where the 

pump begins to ingest air normally; 

this is about the top of the volute. 
The OFF float should be installed 

about halfway down the pump.  If 

a LOW WATER / REDUNDANT 

OFF float is used, then the off float 

should be installed a minimum of 

4 inches above the LOW WATER 

/ REDUNDANT OFF float.

Install the ON / LEAD floats a 

minimum of 4 inches above the 

OFF float.  If additional volume 

is to be pumped on each cycle 

or if the pump running time for 

each cycle needs to be increased, 

then increase the distance from the  

ON / LEAD float to the OFF float 

as needed.
Install the HIGH WATER float 

 

4 inches above the ON / LEAD float.  
For duplex systems install the 

LAG / OVERRIDE float 4 inches 

above the HIGH WATER float.  
On duplex systems where both 

pumps have to run on a daily basis 

to keep up with the incoming flow, 

then the HIGH WATER and the 

LAG / OVERRIDE float position 

should be reversed.

Each pump has an input for the seal 

fail (moisture) sensor commonly 

found in submersible pumps. The 

controller measures the resistance 

of the sensor. In normal operation 

the seal fail condition is set if the 

resistance is less than 2000 ohms. 

One of the option switches can be 

used to change this to set the alarm 

if the resistance is greater than 

2000 ohms. If a seal fail alarm is 

set, then that pump is demoted to 

lag pump and its seal fail lamp and 

output are activated. The seal fail 

does not disable the pump.

Each pump has an input for the 

temperature fail sensor often 

found in pumps. This sensor 

should be shorted if the pump is 

good. If the pump overheats, then 

this sensor will open. The sensor 

is connected to ground and to the 

sensor input for that pump. If the 

pump controller detects an open 

condition in the sensor, then the 

temperature fail lamp and output 

are activated. The temperature fail 

condition will disable the pump. 

The controller can be set using 

an option switch on the bottom 

of the controller to latch up the 

temperature fail condition. If this 

option is selected, then once a 

temperature fail condition is 

detected the fault will not clear 

until the fault condition is cleared 

and the reset push button is pushed 

(or external reset input is closed). 

If this option is not selected, then 

the fault will clear when the sensor 

in the pump closes again.

Each pump has an input which has 

two possible functions. If the fail 

to start test is not activated by an 

option switch on the bottom of the 

controller, these inputs are pump 

disabled.  Under this condition, if 

this input is shorted to ground, then 

that pump will be disabled. If the 

fail to start test is activated these 

inputs are pump running inputs 

and should be shorted to ground 

whenever the pump is running.

Float

Controls

Seal Fail 

Inputs

Temperature 

Fail Inputs

Disable / Pump 

Running Inputs

Summary of Contents for Hydromatic NOVUS 3000 Series

Page 1: ... provide this manual to the owner of the equip ment or to the responsible party who maintains the system NOVUS 3000 STANDARD ELECTRICAL CONTROLS INSTALLATION AND SERVICE MANUAL Item H 03 519 Part 5625 519 1 2012 Pentair Pump Group Inc 11 02 12 ...

Page 2: ...dicator lights and external relay drivers for the following conditions floats out of order seal fail for pumps 1 and 2 temperature fail for pumps 1 and 2 and pump disabled for pumps 1 and 2 Unpacking Panel Remove panel from carton When un pack ing unit check for con cealed damage Claims for damage must be made at the receiving end through the delivery carrier Dam age cannot be processed from the f...

Page 3: ...mally open float switches for level sensing When the tank is empty all of the floats are open The lowest float is the low alarm float If it is not used the low float input should be shorted with a jumper When the tank is empty the controller will be in the low alarm condition On rising water when the level is high enough to close the low float switch then the low alarm will go off As the level ris...

Page 4: ...is run ning Check for flow On three phase power check to see if each pump has prop er ro ta tion Wrong ro ta tion will give low flow 8 Check full load current with amp probe and compare it with the name plate rat ing On three phase pumps check all three phases On single phase pumps check black pump lead 9 Check operation of start relay if supplied on single phase panels per procedure in Item 7ofMa...

Page 5: ...es the resistance of the sensor In normal operation the seal fail condition is set if the resistance is less than 2000 ohms One of the option switches can be used to change this to set the alarm if the resistance is greater than 2000 ohms If a seal fail alarm is set then that pump is demoted to lag pump and its seal fail lamp and output are activated The seal fail does not disable the pump Each pu...

Page 6: ...er or telemetry system There are six switches on the back of the controller which select several different options SW1 When this switch is set the fail to start test is enabled SW2 When this switch is set the temperature fail condition is latched up until reset SW3 When this switch is set the seal fail input is inverted open is fault SW4 When this switch is set the aux relay is the common alarm If...

Page 7: ...inuous sink current 0 4 amps Maximum on resistance 2 ohms WARNING Before handling thesepumpsandcontrols always dis con nect the power first Do not smoke or use sparkable electrical devices or flames in a septic gas eous or possible septic sump 1 Pump does not run in Hand position a Check pump circuit breaker and control fuse for trip ping or blown condition b Check incoming power volt age and cont...

Page 8: ... miswired to ter mi nal block e Voltage and current unbalance Three phase only Voltage un bal ance on three phase power sources can cause motor current to become un bal anced and exces sive heating will re sult Trip ping of the over load protectors and premature motor failures can be expected if the current unbalance exceeds five percent Percent Maximum Current Current Difference from x 100 Unbala...

Page 9: ... lead c Set the amp meter scale to at least 2 times the pump motor full load current d Place the H O A switch in the Hand position to start the pump e The meter should read ap prox i mate ly 2 times full load current during starting f After the motor has started within one sec ond the cur rent should drop to a value much less than full load cur rent 5 Motor voltage check Typical Motor Voltage Comp...

Page 10: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 11: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 12: ...o and from the factory or an authorized Pentair Hydromatic service facility This limited warranty will not apply a to defects or malfunctions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such ser...

Reviews: