63
TROUBLESHOOTING
2. If a temporary jumper between terminals #11 & #12
allows the boiler to proceed to “Trial for Ignition”
then one of the external interlocks (LWCO, etc.) may
be open. Do not leave a jumper installed if there are
interlocks attached to these terminals.
3. Pressing the reset buttons on both high and low gas
pressure switches may reset the error. However, if
this doesn’t reset the error, check the incoming gas
pressure. If it is between 3.5” and 21” of water then
the switches should reset. If the error is occurring at
or after ignition, check the gas pressure when the
boiler lights off. It may be that the gas pressure drops
significantly when the gas valve opens. In this case,
contact the gas supplier to increase the available gas
pressure.
Do not leave a jumper between terminals #11 & #12 if
interlocks are attached to these terminals. Failure to
comply may lead to severe personal injury, death or
major property damage.
CAUTION
5/16"±1/32" 8±1
5/16"±1/32" 8±1
3/16"±1/32" 4.5±1
1 15/16"±1/32" 49.2±1
Figure 10.10: Correct Flame Rod and Ignition Electrode Position
Summary of Contents for PUREFIRE PFC-1000
Page 1: ...PUREFIRE Boilers PFC 850 PFC 1000 PFC 1500 Gas Installation Operation Maintenance Manual ...
Page 82: ...80 Figure 13 4 Control System REPAIR PARTS ...
Page 84: ...82 Figure 13 5 Condensate System REPAIR PARTS ...
Page 90: ...88 APPENDIX C USER MENU APPENDIX C USER MENU Figure C 1 User Menu Managing Burner ...
Page 91: ...89 APPENDIX C USER MENU Figure C 1 User Menu Dependent Burner ...
Page 92: ...90 APPENDIX D INSTALLER MENU STRUCTURE APPENDIX D INSTALLER MENU STRUCTURE ...
Page 93: ...91 APPENDIX D INSTALLER MENU STRUCTURE ...
Page 95: ...93 SERVICE LOG SERVICE LOG Date Serviced By Description of Service Serial Number ...
Page 96: ...94 NOTES ...
Page 97: ...95 NOTES ...