ELECTRICAL CONNECTIONS & INTERNAL WIRING
4.
Relay Module
: This fused module provides isolation
for the pump contacts on the main control board.
The maximum rating for each pump attached is 10
amps. Since only two pumps will operate at any one
time, this limits the incoming power required for this
module to 20 amps. This separate power supply is
to be connected to terminals 27 and 28 on the right
terminal strip.
5.
Integrated Primary Controls
: There are two primary
ignition controls on the
P
ure
F
ire
®
PFC-850, PFC-
1000 and PFC-1500 boiler. They are integrated
controls that supervise all of the ignition timing as well
as the burner modulation. The “managing burner”
control is located in the blower vestibule area and is
mounted adjacent to the top, “managing burner”. The
“dependent burner” control is located adjacent to the
lower “dependent burner.
6.
Supply Temperature Sensors
: The supply temperature
sensors provide input to their respective control which
use them to determine the input rate of each burner.
These sensors are 12k
D
NTC thermistors.
7.
Return Temperature Sensor
: The return temperature
sensors provide information on the boiler return water
temperature to prevent unsafe operation of the boiler.
These sensors are 12k
D
NTC thermistors.
8.
Header Temperature Sensor
: The header temperature
sensor provides the outlet supply temperature of the
boiler to the managing control to control the overall
boiler system operation. These sensors are 12k
D
NTC
thermistors.
9.
Flue Temperature Sensor
: The 12k
D
flue temperature
sensor provides the exhaust vent temperature to the
managing control to prevent unsafe operation of the
boiler.
10.
Supply Limit Switches
: The supply limit switches are
UL353 certified temperature switches that prevent
the boiler from exceeding 210°F (99°C) which is the
maximum operating temperature allowed by ASME
Boiler and Pressure Vessel Code, Section IV. These
switches along with the manual reset circuitry of the
primary controls meet the high limit requirements of
ASME CSDAFB (CSD-1).
11.
Thermal Fuses
: The thermal fuses located at the
rear of each combustion chamber prevent unsafe
operation of the boilers in the event of ceramic
deterioration in the combustion chamber target wall.
12.
Condensate Drain Float Switch
: This switch is
connected to the managing primary control and
prevents the boiler from operating if the condensate in
the condensate collector vessel exceeds its maximum
level.
13.
Blocked Vent Pressure Switch
: This switch is
connected to the managing primary control and
prevents the boiler from operating if the pressure in
the combustion chamber exceeds 4.5 in. w.c. (11
mbar). This will prevent the boiler from operating
with the condensate displaced from the trap due to
pressure.
14.
Flapper Proof-of-closure Switches
: These switches
transmit the position of the flapper to their respective
primary control. If the switch indicates that the flapper
is not closed on the inactive burner while the other
burner is operating, it will start the blower for the
inactive burner. This will assure a positive combustion
chamber pressure and prevent combustion gases from
back-feeding through the inactive burner in the event
of a flapper failure.
Relay module fuses are rated for 10 Amp resistive
load. For inductive loads use 7.5 Amps.
NOTICE
Summary of Contents for PUREFIRE PFC-1000
Page 1: ...PUREFIRE Boilers PFC 850 PFC 1000 PFC 1500 Gas Installation Operation Maintenance Manual ...
Page 82: ...80 Figure 13 4 Control System REPAIR PARTS ...
Page 84: ...82 Figure 13 5 Condensate System REPAIR PARTS ...
Page 90: ...88 APPENDIX C USER MENU APPENDIX C USER MENU Figure C 1 User Menu Managing Burner ...
Page 91: ...89 APPENDIX C USER MENU Figure C 1 User Menu Dependent Burner ...
Page 92: ...90 APPENDIX D INSTALLER MENU STRUCTURE APPENDIX D INSTALLER MENU STRUCTURE ...
Page 93: ...91 APPENDIX D INSTALLER MENU STRUCTURE ...
Page 95: ...93 SERVICE LOG SERVICE LOG Date Serviced By Description of Service Serial Number ...
Page 96: ...94 NOTES ...
Page 97: ...95 NOTES ...