29
2.
Tubing Size
: The connection at the rear of the heat
exchanger is designed for connection to 3/4” ID
PVC or similar tubing. Do not reduce the size of the
condensate drain tubing.
3.
Tubing Pitch
: Be sure that the pipe or tubing is
pitched away from the boiler with a slope of no less
than 1/4” per foot.
4.
Multiple Boilers
: Condensate drain tubes from
multiple boilers should be run separately to prevent
a nuisance lockout of multiple boilers due to a single
clogged drain tube.
5.
Condensate Pumps
: If the boiler drain is above the
level of a gravity drain, a condensate pump should be
used. Table 6.1 lists several available brands. Contact
your PB Heat, LLC Distributor for availability.
CONDENSATE TRAP & DRAIN SYSTEM
Brand Name
Model Number
ITT Bell & Gossett
LS
Little Giant
VCMA-15UL
Beckett
CB151LSUL
Hartell
KT-15-1UL
Table 6.1: Recommended Condensate Pumps
Summary of Contents for PUREFIRE PFC-1000
Page 1: ...PUREFIRE Boilers PFC 850 PFC 1000 PFC 1500 Gas Installation Operation Maintenance Manual ...
Page 82: ...80 Figure 13 4 Control System REPAIR PARTS ...
Page 84: ...82 Figure 13 5 Condensate System REPAIR PARTS ...
Page 90: ...88 APPENDIX C USER MENU APPENDIX C USER MENU Figure C 1 User Menu Managing Burner ...
Page 91: ...89 APPENDIX C USER MENU Figure C 1 User Menu Dependent Burner ...
Page 92: ...90 APPENDIX D INSTALLER MENU STRUCTURE APPENDIX D INSTALLER MENU STRUCTURE ...
Page 93: ...91 APPENDIX D INSTALLER MENU STRUCTURE ...
Page 95: ...93 SERVICE LOG SERVICE LOG Date Serviced By Description of Service Serial Number ...
Page 96: ...94 NOTES ...
Page 97: ...95 NOTES ...