BOILER CONTROL: OPERATION
r. Anti-Cycling Time: This function allows the
installer to set the minimum amount of time that
the boiler can be off on setpoint before recycling.
If the supply temperature drops by a value higher
than Tdiff, the boiler will ignore the minimum off
time and resume operation. If excessive cycling
occurs due to cycling of the thermostat or zone
relay, then the operation of these items should be
examined.
s. System Response Time: To modify the reaction
time of the system for a CH demand, the I-value
parameter can be changed. The following chart
shows the range of values with descriptions of the
corresponding response speed.
Increase this value to reduce cycling in systems
with smaller zones. Decrease this value for a more
aggressive reaction to CH loads. This parameter
effects only the CH response time, a similar
parameter is available in the DHW Settings menu.
t. Maximum Allowable CH Rate: If the boiler is
sized primarily for a DHW load that is significantly
higher than the CH load, this value can be
decreased to limit the input rate of the boiler for
central heating. The following chart shows the
effective input values for various modulation
percentages. As an example, if the DHW load is
1000 MBH and the CH load is 680 MBH, set the
“Max Allowable CH Rate” to 60%.
5.
Domestic Hot Water (DHW) Settings
DHW settings manage the boiler temperature and
circulators for the domestic water heating load. The
boiler can be configured to operate without a domestic
hot water load, with an indirect-fired hot water tank
which incorporates a conventional thermostat, or
with an indirect-fired hot water tank equipped with
a water tank temperature sensor (PB#54157). The
configuration using the optional tank temperature sensor
allows the control to maximize the efficiency of the
system by limiting the input rate to recover from standby
losses.
a. Domestic Hot Water Modes: This menu is used to
change the control response to calls for DHW.
•
Mode 0, No DHW
: Mode 0 indicates that there
is no DHW load. The DHW pump outputs
will be deactivated and the control will not
respond to any signals at terminals #5 & #6.
•
Mode 1, DHW Tank with Sensor
: Mode 1 is
used with a temperature sensor input from the
DHW tank. The optional sensor (PB #54157)
transmits the tank temperature to the control
which allows the control to determine the most
efficient boiler operation to address the heat
demand.
Figure 8.43: DHW Settings – DHW Modes
Table 8.26: DHW Modes
Mode
Display
Input to Terminals
#5 & #6
0
No DHW
None Required
1
DHW Tank
with Sensor
NTC Thermistor
Temperature Input
2
DHW Tank
with Thermostat
Dry Contacts from
DHW Thermostat
Table 8.24: System Response Range & Default
I-Value
Response Time Description
15-20
Very Fast
25-40
Fast
45-80 (Default=60)
Medium
85-110
Slow
115-120
Very Slow
Figure 8.42: CH Settings – Maximum CH Rate
Table 8.25: Maximum CH Rate Range & Default
% Modulation
Input Rate per Burner
PFC-850
PFC-1000
PFC-1500
Btu/hr
Btu/hr
Btu/hr
50%
255
300
450
60%
289
340
510
70%
323
380
570
80%
357
420
630
90%
391
460
690
100%
425
500
750
Table 8.23: Anti-Cycling Ranges & Defaults
Figure 8.41: CH Settings – System Response
Parameter
Minimum
Default
Maximum
Anti-Cycling Time
0 minutes
3 minutes
15 minutes
Anti-Cycling Tdiff
20°F (11°C) 30°F (17°C) 40°F (22°C)
Figure 8.40: CH Settings – Anti-Cycling
Managing Burner Only
Summary of Contents for PUREFIRE PFC-1000
Page 1: ...PUREFIRE Boilers PFC 850 PFC 1000 PFC 1500 Gas Installation Operation Maintenance Manual ...
Page 82: ...80 Figure 13 4 Control System REPAIR PARTS ...
Page 84: ...82 Figure 13 5 Condensate System REPAIR PARTS ...
Page 90: ...88 APPENDIX C USER MENU APPENDIX C USER MENU Figure C 1 User Menu Managing Burner ...
Page 91: ...89 APPENDIX C USER MENU Figure C 1 User Menu Dependent Burner ...
Page 92: ...90 APPENDIX D INSTALLER MENU STRUCTURE APPENDIX D INSTALLER MENU STRUCTURE ...
Page 93: ...91 APPENDIX D INSTALLER MENU STRUCTURE ...
Page 95: ...93 SERVICE LOG SERVICE LOG Date Serviced By Description of Service Serial Number ...
Page 96: ...94 NOTES ...
Page 97: ...95 NOTES ...