41
BOILER CONTROL: OPERATION
a. Last Lockout Error: The last lock menu allows
the user to view the reason for the last lockout.
See Table 10.2 for a list of locking errors and
the associated codes. Note that a value of #255
indicates that there are no lockout errors in the
control history. Also, note that the errors displayed
may have occurred during the factory fire test or
field commissioning of the equipment.
b. Last Blocking Error: The last block screen allows the
user to view the reason for the last blocking error.
See Table 10.1 for a list of blocking errors and the
associated “E” codes. Note that a value of #255
indicates that there are no blocking errors in the
control history. Also, note that the errors displayed
may have occurred during the factory fire test or
during field commissioning of the equipment.
D. INSTALLER MENU
1.
Menu Overview
The installer menu allows installing or service
contractors to view and/or make adjustments to the
permanent boiler settings based on the installation
configuration, desired operation and local codes. The
menu structure is shown in Figure 8.13.
To access the installer menu, press and hold the
“Menu” and “Select” key on the LCD display
corresponding to the burner on which the parameter
change is to be made.
a. Managing Burner (Burner M): The top burner on
each PFC-850, PFC-1000 or PFC-1500 boiler is
designated as “Burner M” or “managing burner”.
This burner control is connected to the GEN
(Boiler) circulator, the CH and/or DHW circulator*
and all external sensors*. In the following section,
all parameters which affect only the managing
burner will be designated with “(M)”.
*
Stand-Alone configuration or Master Boiler
in multiple boiler configuration.
b. Dependent Burner (Burner D): The bottom burner
on each boiler is designated as the “Burner D” or
“dependent” burner. This burner control is started
and stopped by the managing burner only. Its
operation is not affected by external inputs.
2.
Status
The status menu is designed to monitor key
parameters and aids the installer or service contractor
in determining if there are problems with boiler
operation.
a. Current Supply Setpoint: The setpoint value
will change for DHW demands or CH demands
depending on the setpoint chosen for these modes
of operation. When outdoor reset modes are
selected, this value is the calculated target for the
system.
b. Fan Speeds: Screens #2 & #3 display fan speed
information. The current fan speed will vary
during operation between the low power and
high power values. The Low Power, Ignition,
and Hi Power values are preset at the factory for
a specific model size. Table 12.3, in Section 12
of this manual, shows the fan speed presets for
each model size. Note that these values may vary
slightly due to air setting changes.
c. Flame Measurements: Screens #4, #5 & #6
display flame signal information. The first value,
Flame Signal, is the current flame rectification
signal in micro amps (µA). The minimum value
for this signal that will allow the burner to continue
running is 2.8 µA the maximum value for this is 10
µA.
Figure 8.12: Messages – Last Errors
Figure 8.13: Installer Menu
Figure 8.14: Status – Supply Setpoint
Figure 8.15: Status – Fan Speeds
Figure 8.16: Status – Flame Signal
Summary of Contents for PUREFIRE PFC-1000
Page 1: ...PUREFIRE Boilers PFC 850 PFC 1000 PFC 1500 Gas Installation Operation Maintenance Manual ...
Page 82: ...80 Figure 13 4 Control System REPAIR PARTS ...
Page 84: ...82 Figure 13 5 Condensate System REPAIR PARTS ...
Page 90: ...88 APPENDIX C USER MENU APPENDIX C USER MENU Figure C 1 User Menu Managing Burner ...
Page 91: ...89 APPENDIX C USER MENU Figure C 1 User Menu Dependent Burner ...
Page 92: ...90 APPENDIX D INSTALLER MENU STRUCTURE APPENDIX D INSTALLER MENU STRUCTURE ...
Page 93: ...91 APPENDIX D INSTALLER MENU STRUCTURE ...
Page 95: ...93 SERVICE LOG SERVICE LOG Date Serviced By Description of Service Serial Number ...
Page 96: ...94 NOTES ...
Page 97: ...95 NOTES ...