WaveStar Static Transfer Switch 2000A 3-Pole
84
Ctrl Nr: PM375118-004
15
Digital and Analog Points
15.1
Digital Screen Points
Table 5 shows the digital points as they show on the screen for the Digital Points List (Rev 2.86 and higher).
The Normal and Abnormal columns show what is Normal for the digital point (and hence not an alarm) and
what is Abnormal (hence an alarm). These columns are meaningful only for points that are Alarms (as noted
in the Alarm column).
Example:
“Retransfer” (point 8) is not an alarm (“No” in Alarm column).
The same point name is used when the point appears on the Digital Values Screen, the Event Log Screen, or the
Alarms Screen. The status for digital points is in an adjacent table following the list of points.
Custom STSs will have different points and the current points list may not apply.
Table 5 Digital Screen Points
Name
Normal Abnormal Alarm
Alarm
Index
Status
Status
Index
Normal
Value
Isolation 1 MCSW Closed Open
Yes
1 Yes
1001
1
Isolation 2 MCSW Closed Open
If Installed
2 Yes
1002
1
Bypass 1 MCSW Open Closed
Yes
3 Yes
1003
0
Bypass 2 MCSW Open Closed
Yes
4 Yes
1004
0
Input 1 MCSW Closed Open
Yes
5 Yes
1005
1
Input 2 MCSW Closed Open
Yes
6 Yes
1006
1
Override
No
Yes
No
7
1007
0
Retransfer
Yes
No
No
8 Yes
1008
1
ROI in Control
No
Yes
Yes
9 Yes
1009
0
Preferred Source
1
2 No
10 Yes
1010
0
PDU 1 CB
Closed Open
If Installed
11 If Installed
1011
1
PDU 2 CB
Closed Open
If Installed
12 If Installed
1012
1
Building 1
OK
Alarm
If Installed
13 If Installed
1013
0
Building 2
OK
Alarm
If Installed
14 If Installed
1014
0
Building 3
OK
Alarm
If Installed
15 If Installed
1015
0
Building 4
OK
Alarm
If Installed
16 If Installed
1016
0
Building 5
OK
Alarm
If Installed
17 If Installed
1017
0
Building 6
OK
Alarm
If Installed
18 If Installed
1018
0
Building 7
OK
Alarm
If Installed
19 If Installed
1019
0
Building 8
OK
Alarm
If Installed
20 If Installed
1020
0
Output Short
OK
Alarm
Yes
21 No
1021
0
Open S1
OK
Alarm
Yes
22 No
1022
0
Open S2
OK
Alarm
Yes
23 No
1023
0
EPO
OK
Alarm
Yes
24 No
1024
0
Remote EPO OK
Alarm
If Installed
25 No
1025
0
XFMR 1 HT
OK
Alarm
If Installed
26 If Installed
1026
0
XFMR 1 OT
OK
Alarm
If Installed
27 If Installed
1027
0