System Setup: Networking
Ctrl Nr: PM375118-004
61
10.2
Ethernet
The STS has an Ethernet port and cable. (For physical attachment see
5.2 Ethernet Connection
.) The
Ethernet cable must be physically attached to the customer network and STS Ethernet addresses set
before ModBus TCP/IP, SNMP, or SNTP Time Synchronization are configured.
The
Ethernet Settings
panel in the
Settings
screen
(Figure 24) allows the operator to set an IP address
if a different address than the DHCP address is required.
•
Address
is the Ethernet IP address of the Switch, which can be set directly or by DHCP.
•
If the
Use DHCP
has a green check mark (
√
), the DHCP address will be used for the
IP address in
Address
.
•
If the
Use DHCP
icon has a red X, DHCP is not used to set the IP address. Enter an
IP address in
Address
for the Switch.
•
Press
Mask
to enter Ethernet IP mask address.
•
Press
Gateway
to enter Ethernet Gateway.
•
MAC
ID is set in the factory and cannot be changed.
•
Toggle
Use DHCP
button:
•
Green check mark: Use DHCP to assign IP address.
•
Red X: Do not use DHCP; use
Address
IP value.
•
Stat
button: shows communications statistics (a service function)
•
Restart
button: restarts the Monitor. On the ROI, the Mode of Operation must be set to
Redundant
so that there is a backup transfer process during the restart.
NOTE:
The Monitor must be restarted when
Ethernet Settings
change.
10.3
Time Settings
Time stamps are important data for log entries and alarms. The STS clock should be synchronized with
clocks in other equipment to accurately diagnose problems affecting multiple systems. You can set the
STS clock manually or with the Time Synchronization feature.
10.3.1
Manual Time Setting
To manually set the clock, enter a date and time in
Time Settings
on the
Settings
screen
.
Press the
Set
button, which will bring up the
Keyboard
Screen. Enter time and date.
10.3.2
Time Synchronization Settings Screen (SNTP)
The Time Synchronization feature with SNTP requires the STS Ethernet connection.
Prerequisites:
1. The
Ethernet Settings
on the
Settings
screen must be configured.