Message on
the display
Cause
Related function
Required for re-commissioning
Standalone
controller
Cascade
controller
Blocking pro-
tection active
Blocking protection activated and current-
ly active for pumps and valves
-
Î
Deactivate blocking protection.
Yes
Yes
Desinf.
successful the
[##.##.##]
Disinfection function completed success-
fully, disinfection temperature for required
disinfection duration reached
-
-
Yes
Yes
Disinf.temp.
for [## Min.]
exceeded
During and after completion of the disin-
fection, the temperature at the Circ. RET
sensor exceeds the value (T-Disinf. set
- 5 K) for the defined duration.
-
-
Yes
Yes
max. temp at
Circ. RET
[## °C]
Disinfection function completed success-
fully, indication of the highest measured
temperature at the Circ. RET sensor.
-
-
Yes
Yes
Everything OK -
-
-
Yes
Yes