31
en
Message on
the display
Cause
Related function
Required for re-commissioning
Standalone
controller
Cascade
controller
!Sensor fault
Temperature sensor fault
- Function using this sensor
After repair, the function will automatically be
reactivated and the error message deleted.
Yes
Yes
!T-FL
T-ST_FL sensor fault
- Sliding set temperature
- Cold start function
- Comfort function
After repair, the function will automatically be
reactivated and the error message deleted.
Yes
Yes
!T-HW
T-HW sensor fault
- DHW heating and store loading
- Cold start function
- Circulation
- Thermal disinfection
- Heat quantity measurement
After repair, the function will automatically be
reactivated and the error message deleted.
Yes
Yes
!T-CW
T-CW sensor fault
- Circulation
- Heat quantity measurement
- Thermal disinfection
After repair, the function will automatically be
reactivated and the error message deleted.
Yes
Yes
!Flow rate
Flow rate sensor fault
- DHW heating and store loading
- Circulation
- Thermal disinfection
- Heat quantity measurement
After repair, the function will automatically be
reactivated and the error message deleted.
Yes
Yes
!Primary
circuit
Fault in the primary circuit (primary pump
fault)
- DHW heating and store loading
- Cold start function
- Comfort function
After repair, the function will automatically be
reactivated and the error message deleted.
No
Yes
!Circulation
pump
Circulation pump fault
- Circulation (if Circ.pump = active)
After repair, the error message will automat-
ically be deleted.
Yes
Yes
!T-FL too low Store flow temperature too low for
reaching the hot water set temperature
-
After repair, the error message will automat-
ically be deleted.
No
Yes
!Cont. pump
operation
Primary pump permanentely on
- DHW heating and store loading
- Cold start function
- Comfort function
Î
After repair, manually acknowledge the
error message.
After repair, the functions will automatical-
ly be activated, the module be available for
cascade operation and the error message
deleted.
Yes
Yes
No message
on the display
Overtemperature protection function
- DHW heating and store loading
If T-HW > T-HW set, the primary pump will
automatically be activated.
Yes
Yes
Emergency
operation
Emergency operation of the primary
pump has been activated by user and
pump is active in emergency mode
- DHW heating and store loading
Î
Deactivate emergency mode.
Yes
Yes