18
en
3.3
Store loading
In this menu, all adjustments for the DHW heating and loading of the secondary
store can be made. The following parameters and functions are available:
• Emergency operation
• Hot water set temperature / Set temperature secondary circuit fl ow
• Minimum hot water set temperature / minimum set temperature secondary
circuit fl ow
• Maximum hot water set temperature / maximum set temperature secondary
circuit fl ow
• Sliding set value
• Blocking protection
Emergency operation
Main menu / Store loading / Emergency operation
Adjustment
channel
Description
Adjustment
range / selection
Factory
setting
Emergency
operation
Activation of the function
Yes, No
No
Em. prim.
Emergency speed of the primary pump
1.5 … 100.0 %
30.0 %
Em. sec.
Emergency speed of the secondary pump
1.5 … 100.0 %
30.0 %
T-HW
Indicates the current fl ow temperature in the sec-
ondary circuit for aligning the emergency speed.
-
-
back
The Emergency operation function can be used for ensuring the hot water
supply and loading of the secondary store in the case of a sensor fault. In this case
the pumps will run at the adjustable Em. prim. and Em. sec. For this purpose,
the emergency speed must be aligned with the resulting temperature at the hot
water fl ow sensor in the secondary circuit. The display channel
T-HW allows this
alignment directly in the Store loading menu, as soon as the emergency operation
has been activated.
Note:
If a sensor fault inhibiting DHW heating or store loading has occurred,
activate the emergency operation in the Emergency mode channel.
In order to ensure a quick entry to emergency operation in the case of an emer-
gency, perform the alignment of the emergency speed as early as possible.
Hot water set temperature / Set temperature secondary circuit fl ow
(T-HW set)
Main menu / Store loading / T-HW set
Adjustment
channel
Description
Adjustment range /
selection
Factory
setting
T-HW set
Hot water set temperature / Set temperature
secondary circuit fl ow (T-HW set)
20 … 75 °C
60 °C
This parameter can be used for adjusting the T-HW set temperature which is to
be reached at the HW fl ow sensor. This temperature is also used for loading the
secondary store. The controller then determines the pump speed of the primary
pump such that the temperature at the HW fl ow sensor in the secondary circuit
continuously keeps the required set temperature T-HW set.
Note:
If the SUS Sys 2, 3 variants have been selected and the circulation function
is active, T-HW set cannot be adjusted to a value smaller than (T-circ
on +
∆
T-circ off + hysteresis).