![PAW FC4.13 Manual For Specialised Craftsman Download Page 29](http://html.mh-extra.com/html/paw/fc4-13/fc4-13_manual-for-specialised-craftsman_764036029.webp)
29
en
Directional pad flashes red.
Sensor fault. The error code !Sensor fault is
displayed instead of a temperature on the sensor
display channel.
5
Troubleshooting
If a malfunction occurs, a message will appear on the display of the controller.
fuse
The controller is protected by a fuse. The fuse holder (which also holds the spare
fuse) becomes accessible when the cover is removed. To replace the fuse, pull the
fuse holder from the base.
WARNING!
Electric shock!
Upon opening the housing, live parts are exposed!
Î
Always disconnect the controller from power supply
before opening the housing!
The display is permanently off.
Press button
➄
. Display illuminated?
no
yes
Controller has been in
standby, everything o.k.
Check the supply line and recon-
nect it.
The fuse of the controller could be
blown. The fuse holder (which holds
the spare fuse) becomes accessible
when the cover is removed. The
fuse can then be replaced.
Check the power supply of the controller. Is it disconnected?
no
yes
°C
Ω
Pt1000
°C
Ω
Pt1000
-10
961
55
1213
-5
980
60
1232
0
1000
65
1252
5
1019
70
1271
10
1039
75
1290
15
1058
80
1309
20
1078
85
1328
25
1097
90
1347
30
1117
95
1366
35
1136
100
1385
40
1155
105
1404
45
1175
110
1423
50
1194
115
1442
Short circuit or line break
Disconnected temperature sensors can be
checked with an ohmmeter. Please check if the
resistance values correspond with the table.