Bulletin 76-00 B
15
Remote Communications Setup Instructions - Option 1
Steps
Setup Instructions
Display
Notes
9
The following window will
appear. Ensure that ‘Receive’ and
‘Transmit’ are both set to 4096, and
that ‘Latency Timer’ is set to 1.
10
Click on the 'COM Port Settings'
in the Remote Communications
application to set up the COM Port.
11
Select the COM port that is
associated with the RS485 cable.
It is important to select the correct COM port that
aligns with the RS-485 converter. This can be
determined by starting the application on the PC
with the RS485 converter unplugged from the V300
Purger Controller, then look at the COM ports that
are available on the Bootloader. Then, plug in the
RS485 converter and click 'Find COM Ports' in the
application. The additional COM port that appears
is the port that should be selected.
12
Set the Baud Rate to '19200'
Set the Parity to 'Even'
Keep the Refresh Rate to '5'
Seconds
13
Press 'Apply' to set the parameters
and return to the Main Screen.
Then press ‘Connect’ on the Main
Screen to establish a connection.
If connection is properly established, the real time
display will appear in the remote communications
application:
From here on, remote monitoring and setting is
enabled via the application.