background image

Bulletin 76-00 B

3

Pressure Transducer

Suction
Line

Vent 

Solenoid

Bubbler

Water Inlet

Water
Drain
line

Level
Sensor

Heat 
Exchanger

Oil

Drain

Foul Gas line

Liquid 

Drainer

Check Valve 

w/ Orifice

Liquid 

Refrigerant 

Line

Check 

Valve w/ 

Orifice

Liquid

Solenoid

w/ Check 

Valve 

& Orifice

Vapor Vent

Flow 

Controller

Check Valve
w/ Orifice

Flow 

Controller

Low Temp. Liquid

High Pressure Gas

Non-Condensable 
Gases

Water

Pressure Transducer

Suction
Line

Vent 

Solenoid

Bubbler

Water Inlet

Water
Drain
line

Level
Sensor

Heat 
Exchanger

Oil

Drain

Foul Gas line

Liquid 

Drainer

Check Valve 

w/ Orifice

Liquid 

Refrigerant 

Line

Check 

Valve w/ 

Orifice

Liquid

Solenoid

w/ Check 

Valve 

& Orifice

Vapor Vent

Flow 

Controller

Check Valve
w/ Orifice

Flow 

Controller

Low Temp. Liquid

High Pressure Gas

Non-Condensable 
Gases

Water

A higher temperature measured at this point, compared to the 
saturation pressure, indicates the presence of non-condensable 
gases in the system .

Purging non-condensable gas from a refrigeration system can be 
accomplished manually, mechanically or automatically . Manual 
purging generally involves personnel removing air from specified 
purge “points” within the system through hand shut off valves 
routed to a water bucket . Mechanical purging is achieved by use 
of a device which will allow air to escape to a water reservoir 
when air is present . The latter method is automatic purging, 
which is generally achieved by the use of a self-contained system 
incorporating microprocessor controls . These are designed to 
sample the non-condensable gases and refrigerant mixture and 
purge when non-condensable gases are present .

Mechanical and automatic air purging units, commonly referred 
to as “purgers”, are manufactured by several companies . Each 
manufacturer’s purger operates in its own unique way . This article 
will focus specifically on the automatic purgers manufactured by 
Parker Hannifin Refrigerating Specialties Division .

The most common purge points in a refrigeration system are at 
the condenser drain, pilot receivers, thermosyphon receivers, 
high pressure receivers, liquid drain header, equalizing lines, 
and low velocity-high side areas .

Purge points should be located to ensure no liquid refrigerant 
is drawn into the purger .  The Rapid Purger V300 has a liquid 
drainer at the foul gas inlet to prevent any liquid refrigerant from 
entering the shell side of the heat exchanger .

Figure 2: 

Purger Fill & Pre-Cool Cycle

Purge Cycle

The purge cycle consists of three main processes:  fill & pre-cool, 
separation of non condensable gases & refrigerant, and the safe 
release of the non-condensable gases .   

1 .  Fill & Pre-Cool (See Figure 2 for a graphic representation of 

this cycle)

This cycle begins with high pressure liquid ammonia feeding 
through the liquid solenoid, check valve and orifice (causing 
expansion) into the V300’s heat exchanger . The liquid 
solenoid stays energized until the level of ammonia in the 
heat exchanger is sensed by the level sensor . The level sensor 
is strategically located so that all of the tubes in the heat 
exchanger are filled with liquid ammonia . This guarantees 
the highest level of performance . 

The V300 Rapid Purger will stay in the “Pre-Cool” mode until 
the shell of the heat exchanger reaches a temperature of 4 .4ºC 
(40ºF) or lower . This is determined by the temperature of the 
suction the purger is tied into . Once the purger reaches the 
required temperature, the purger will enter the active mode .

To prevent a vacuum type situation, the A2B evaporator 
pressure regulator, located on the return suction line, is set at 

Figure 3: 

Purger Separation of Non-Condensable Gases & 

Refrigerant Cycle

0 .34 barg (5 psig) . This will prevent the heat exchanger from 
reaching temperature below -29ºC (-20ºF) .  

2 .  Separation of Non-Condensable Gases & Refrigerant (See 

Figure 3 for a graphic representation of this cycle)

Once the fill and pre-cool cycle reaches the desired 
temperature and liquid level, it selects a purge point and 
commences a purge cycle by activating a solenoid located on 
the high side of the system, as illustrated in Figure 1 .

With an active purge point, the non-condensable gases and 
refrigerant mix, also known as foul gas, enters the shell side 
of the heat exchanger through the liquid drainer, check valve 
and a flow control orifice . Any liquid that has condensed in 
the purge lines will collect in the liquid drainer and return 
directly to the suction . If the foul gas line does not contain 
condensed liquid and any remaining liquid in the liquid 
drainer evaporates to the suction, the liquid drainer flow 
control ball will prevent any foul gas from entering the 
suction line by blocking the orifice at the bottom of the liquid 
drainer tank, forcing the foul gas through the flow control 
orifice . 

*Graphics for illustration only .

*

*

Summary of Contents for V300

Page 1: ...ble are now accessible via the serial channel Further advancements include extended data logging time and password protection for factory calibration settings Like its predecessor the V200 the V300 ca...

Page 2: ...ointers 22 Purge Point Initiation Termination Instructions 25 Setting Communications and Unit Instructions 27 Display Setting Instructions 28 Language Setting Instructions 29 Date Time Setting Instruc...

Page 3: ...the foul gas inlet to prevent any liquid refrigerant from entering the shell side of the heat exchanger Figure 2 Purger Fill Pre Cool Cycle Purge Cycle The purge cycle consists of three main processes...

Page 4: ...e 4 for a graphic representation of this cycle Non condensable gases will continue to accumulate in the Vapor Vent Float chamber as it is separated from the refrigerant Once the volume of these gases...

Page 5: ...ding 4 Remove the purger flange connections with the welded stubs from the high pressure liquid foul gas and suction line The flanges are highlighted in gray in Figure 6 5 Wait several minutes before...

Page 6: ...water level press and hold the INIT button on the controller keypad to energize the water solenoid valve When water begins to drain from the overflow tube release the INIT button to de energize the w...

Page 7: ...selection bar does not have Start Up selected use the or button to move the selection bar 3 Follow the instructions on the screen and then press Enter BEFORE SETTING PURGE CYCLE CHECK THAT WATER MAKE...

Page 8: ...TEMPERATURE CALIBRATE PRESSURE INPUT SETUP MENU SET PASSWORD If the selection bar does not have the Set Password option selected use the or button to move the selection bar 4 Use the and buttons follo...

Page 9: ...Purge Type menu select either Auto Manual or Time Based by using the or button to move the selection bar and press Enter AUTO SELECT WITH PRESS ENTER PRESS MENU TO RETURN MANUAL TIME BASED PURGE TYPE...

Page 10: ...END TIME 11 20 PM START END TIME REVIEW To cancel the operation press Menu to return to the beginning of the Stop Time setting screens 13 Use the or buttons to select the number of Purge Points in the...

Page 11: ...s to select the minimum pressure and press Enter to set the value ADJUST THE MIN PRESSURE ADJUST WITH PRESS ENTER PRESS MENU TO RETURN PRESSURE SENSOR MIN ADJUST 0 PSI The default value is the factory...

Page 12: ...RS 485 422 interface converter see Figure 11 below Remote Communications Setup Assembly Instructions To connect the CAT5 Ethernet cable to the GM 482422 converter follow below instructions 1 Measure...

Page 13: ...r located in the drive containing the Gearmo CD D drive 3 Now open the folder which corresponds to the operating system on your computer of choice in this case it is win xp server 2003 2008 Vista 7 8...

Page 14: ...e 6 Plug in the RS845 Cat5 connector to the RJ45 Jack on the Display Board affixed to the backside of the Enclosure lid The adaptor s driver should be installed on the laptop for the w port to be reco...

Page 15: ...h the RS485 converter unplugged from the V300 Purger Controller then look at the COM ports that are available on the Bootloader Then plug in the RS485 converter and click Find COM Ports in the applica...

Page 16: ...ERM on the Main Screen 18 The following screen will appear Select Terminate Point to terminate the current purge point and cycle to the next Select Terminate Cycle to end purging completely 19 Click V...

Page 17: ...mputer 4 Open the V300 Purger Controller enclosure by unlatching the two side latches 5 Feed the other end of the cable RS845 side through an unused hole at the bottom of the V300 Purger Controller en...

Page 18: ...ent Date 0x01 0x56 2 Current Day of Month 01 to 31 set month and year first to ensure that the day of month is valid for the current month 0x0D VALUE 1 1 VALUE 2 2 VALUE n n Current Month 0x01 0x57 2...

Page 19: ...protrude from the packing nut This will prevent liquid ammonia from being trapped between the liquid hand shut off valve and SV2 solenoid 4 Use the HSBR level switch as a ammonia level indicator When...

Page 20: ...7 5 Liquid Refrigerant Line Non Condensables Vent Line Water Inlet Line Foul Gas Line Water Drain Line 37 5 31 14 33 Suction Line 38 11 21 20 6 7 8 29 28 27 27 25 1 22 24 21 5 13 4 15 10 12 10 12 Figu...

Page 21: ...Valve Water Line Nylon Connector Elbow Solenoid Valve Assembly Water Line 208787 20 6 21 4 Nylon Tubing Nylon Connector Elbow Nylon Tubing Bubbler 208668 22 Water Bubbler Water Bubbler Assembly 20878...

Page 22: ...d and no field adjustment is required If the main controller displays _ _ _ rather than an actual temperature reading check for loose wires Check wire loom from main board to cover for loose or damage...

Page 23: ...r for optimal performance If the use of Refrigerating Specialties coils is not an option coils with an inrush current rating of less than 1 22 amps MUST be used If this symptom is presented it is reco...

Page 24: ...Bulletin 76 00 B 24 A A P P E N D I X...

Page 25: ...ive Points are present LIQUID SOL VENT WATER SOL THU MAY 21 15 04 10PM WAIT NO ACTIVE POINTS ACTUAL TARGET 16 F 99 3 PSIG VENT 56 4 PSIG 79 3 PSIG RESET CYCLE HISTORY PT VENTS TOTAL TIME MODE MANUAL 6...

Page 26: ...rge cycle will always change the mode to Manual 10 The screen now indicates that No Active Points are present and the mode has changed to Manual LIQUID SOL VENT WATER SOL THU MAY 21 15 04 10PM WAIT NO...

Page 27: ...After moving the selection bar to the option you would like to change press the ENTER button 4 Use the or buttons to make parameter changes within the selected option SETTINGS MENU SOFTWARE VERISON 2...

Page 28: ...eases the contrast 4 Press the ENTER button to return to the display setting menu screen CONTRAST ADJUST SELECT WITH PRESS ENTER PRESS MENU TO RETURN 5 To change the backlight move the selection bar t...

Page 29: ...have the set date and time option selected use the or button to move the selection bar 5 Select the current year by using the or button to increase or decrease the year When the year is selected pres...

Page 30: ...time menu Follow step 13 of the date time setting instructions to exit to the main menu screen 10 Select the current minute by using the or button When the minute is selected press ENTER to continue t...

Page 31: ...format by using the or button to move the selection bar and press ENTER MON DD YY SELECT WITH PRESS ENTER PRESS MENU TO RETURN DD MON YY MM DD YY DD MM YY SET DATE FORMAT CURRENT DATE TUE AUG 05 14 Mo...

Page 32: ...RENT WEEK PG PT 01 CHANGE WITH AND LBS 00 02 00 07 00 07 00 06 00 07 00 03 00 07 Vents represents the total vents on a given Day and Purge Point Time represents the total time of all vents on a given...

Page 33: ...or button to move the selection bar 3 Use the or button to move the selection bar to the Clear History option and then press Enter READ POINT HISTORY SELECT WITH PRESS ENTER PRESS MENU TO RETURN CLEA...

Page 34: ...N SETUP FACTORY TEST MODE HISTORY MAIN MENU LANGUAGE MENU If the selection bar does not have Factory Test Mode selected use the or button to move the selection bar 3 Enter the new password by using th...

Page 35: ...Bulletin 76 00 B 35...

Page 36: ...er device is opened or removed Flanges with ODS connections are not suitable for ammonia service Warranty All Refrigerating Specialties products are under warranty against defects in workmanship and m...

Reviews: