Bulletin 76-00 B
11
Calibrate Pressure Input and RTD
Steps
Setup Instructions
Display
Notes
1
To calibrate the Pressure Input or the
RTD, press the (MENU) button to go to
the secondary menu screen
START UP
SELECT WITH
∨ ∧
PRESS (ENTER)
PRESS (MENU) TO RETURN
SETUP
FACTORY TEST MODE
HISTORY
MAIN MENU
LANGUAGE MENU
2
Use the (
∨
) button to move the selection
bar to the 'Setup' option and then press
(Enter)
START UP
SELECT WITH
∨ ∧
PRESS (ENTER)
PRESS (MENU) TO RETURN
SETUP
FACTORY TEST MODE
HISTORY
MAIN MENU
LANGUAGE MENU
If the selection bar does not have the 'Setup' option
selected, use the
(
∧
) or (
∨
) button to move the selection
bar.
3
Use the (
∨
) button to move the selection
bar to either 'Calibrate Pressure Input' or
'Calibrate RTD (Temperature)' and then
press (Enter).
SET DATE AND TIME
SELECT WITH
∨ ∧
PRESS (ENTER)
PRESS (MENU) TO RETURN
PURGE OPTIONS
CALIBRATE RTD (TEMPERATURE)
CALIBRATE PRESSURE INPUT
SETUP MENU
SET PASSWORD
If 'Calibrate Pressure Input' is selected, jump to Step 4
If 'Calibrate RTD (Temperature)' is selected, jump to Step 8
4
Use the (
∧
) and (
∨
) buttons followed by
(Enter) for each of the four digits of the
password
PLEASE ENTER THE PASSWORD
ADJUST WITH
∨ ∧
PRESS (ENTER)
OR PRESS (MENU) TO GO BACK
0
0
0
0
PASSWORD RESTRICTED MENU
The Pressure input valves will not be accessible without
the correct password
5
Use the (
∧
) and (
∨
) buttons to select the
minimum pressure and press (Enter) to
set the value
ADJUST THE MIN PRESSURE
ADJUST WITH
∨ ∧
PRESS (ENTER)
PRESS (MENU) TO RETURN
PRESSURE SENSOR MIN ADJUST
0 PSI
The default value is the factory calibrated value
6
Use the (
∧
) and (
∨
) buttons to select the
maximum pressure and press (Enter) to
set the value
ADJUST THE MIN PRESSURE
ADJUST WITH
∨ ∧
PRESS (ENTER)
PRESS (MENU) TO RETURN
PRESSURE SENSOR MAX ADJUST
500 PSI
The default value is the factory calibrated value
7
This screen gives the opportunity to
check if all the values for calibrating the
pressure input are correct. If everything
entered is correct, press (Enter) to make
the changes
CURRENT VALUES:
SELECT WITH
∨ ∧
PRESS (ENTER)
OR PRESS (MENU) TO GO BACK
MIN PRESSURE: 0 PSI
MAX PRESSURE: 500 PSI
PRESSURE SENSOR MIN / MAX
Press (Enter) two more times to get back to the Main Menu
8
Use the (
∧
) and (
∨
) buttons followed by
(Enter) for each of the four digits of the
password
PLEASE ENTER THE PASSWORD
ADJUST WITH
∨ ∧
PRESS (ENTER)
OR PRESS (MENU) TO GO BACK
0
0
0
0
PASSWORD RESTRICTED MENU
9
Use the (
∧
) and (
∨
) buttons to set the
ambient RTD temperature and press
(Enter) to set the value
SELECT WITH
∨ ∧
PRESS (ENTER)
OR PRESS (MENU) TO GO BACK
CURRENT RTP TEMP: 49° F
RTP (TEMPERATURE) CALIBRATE
The default value is the factory calibrated value
Press (Enter) two more times to get back to the Main Menu
Do not adjust calibration to increase the number of vents
Note: Factory calibration of the RTD may have created an
offset less than or greater than 0.
Calibrate Pressure Input and RTD