background image

SECTION 1  MOUNTING & PIPING INSTALLATION

An APM is usually installed in the compressor room where 

it can be monitored, but also may be installed outdoors 
where temperatures below freezing are not anticipated.  

The APM comes standard with a watertight NEMA 13 (IP65, 

Category 2) control cabinet enclosure with sealed conduit 
wiring.  Any unused electrical entrances to the enclosure 
must be sealed to protect electronics from moisture. A 
NEMA 4 cabinet enclosure is available.

An optional valve package (VPM) for purger isolation is 

available from Hansen. This consists of three welded 
assemblies which include shut-off valves, gauge valves, 
and mating flanges. An illustration detailing this optional 
valve package is on page 12 (Figure 13).

FOUL GAS PIPING

Purging at several points, up to four with the APM, on the 
high-pressure side of the system is the best method for 
removing foul gas. Foul gas is refrigerant gas containing 
some air or other noncondensibles.  Several points should 
be used because it is nearly impossible to predict where 
noncondensible gas will accumulate in a system.

Even for multipoint purging, only one purge point should be 
purged at a time.  Connecting two purge points from two 
condensers or receivers may result in gas flowing from one 
condenser to another.  This is due to an unequal pressure 
drop, even though the differences in pressure drop are 
very small, for example ¼ psig (0.02 bar).  The result would 
be that, even in the best of circumstances, only one point 
is effectively purged.  The best practice is to purge each 
condenser and receiver circuit separately.

When utilizing multipoint purging, the purge point solenoid 
valves can be manifolded into one foul gas line to the 
purger.  A ½" (13 mm) size line is the minimum and should 
be pitched toward the purger to drain any condensed 

liquid.  Also, no liquid traps are allowed either before or 

after the purge point solenoid valves (See Figure 2).  The 
foul gas line should not pass through cold areas where 

INTRODUCTION

The AUTO-PURGER® M is a compact and totally automatic, 

electronically-controlled, noncondensible gas refrigerant 
purger for reducing condensing pressure, and thereby 
saving electrical energy used by the refrigeration system.  

This deluxe purger is preassembled, prewired, tested, 

insulated, and includes an automatic water bubbler.  
Installation requires piping the foul gas line, liquid line, 
suction line, water line, drain line, and wiring the power 

connection and the remote ½" (13 mm) port purge point 
solenoid valves, which must be purchased separately.  Up 
to four (4) purge points can be controlled by this purger.  

The AUTO-PURGER® M (APM) features welded piping 

and watertight electrical construction.  The APM meets 
the requirements of the Canadian Standards Association 
(CSA certified).

A typical APM installed in a plant with normal-entering 

noncondensible loads will handle up to a 200 ton (700 kW) 
system.  Each purge point will be active between 10 and 30 
minutes, depending on the noncondensible gas presence 
(mostly air) and the purger mode of operation.

Model APMF AUTO-PURGERS are for use in halocarbon 
refrigeration systems. The installation and operation of 
these AUTO-PURGERS are similar to that of an ammonia 

AUTO-PURGER M. See page 13 for additional details.

MOUNTING INSTRUCTIONS

Mount the APM straight and securely on a wall or sturdy 
steel channels capable of supporting 350 lbs (160 Kg). Eight 
mounting holes in the frame are provided to support the 
purger (See Figure 1). The APM should be located in an 
accessible area, but away from the movement of equipment 
that could accidentally damage the purger. Elevation with 
respect to condensers or high-pressure receivers is not 
critical, however, purge point solenoid valves must be 
above the purger. 

Specifications, Applications,        

Service Instructions & Parts

AUTO-PURGER

®

 M 

“Energy Saver”

Compact, Non-condensible 

Gas (Air) Purger

Bulletin APM-001e

AUG 2015

 For Models APM & APMF 

Model APM 

Summary of Contents for AUTO-PURGER M

Page 1: ...ore or after the purge point solenoid valves See Figure 2 The foul gas line should not pass through cold areas where INTRODUCTION The AUTO PURGER M is a compact and totally automatic electronically co...

Page 2: ...ndenser piping design Hansen Technologies can provide copies of these articles Also consult the condenser manufacturers installation instructions for additional piping and sizing information On evapor...

Page 3: ...E CLOSE COUPLED ISOLATION TO PURGER 1 2 13 MM PORT SHUT OFF VALVE REMOTE PURGE POINT SOLENOID VALVE ISOLATION SHUT OFF VALVE STRAINER GLOBE VALVE STEM HORIZONTAL IS PREFERRED LEVEL OR PITCH DOWN SECTI...

Page 4: ...oil will not be a problem unless the liquid line is connected to a vessel or line where oil can enter the purger See also the Caution section on page 14 Escaping refrigerant may cause personal injury...

Page 5: ...il voltage is different simply remove and discard the factory installed jumpers between terminals 13 14 and 15 16 Bring the purge point solenoid line L1 connection to terminal 14 and neutral L2 to ter...

Page 6: ...e gases that may have collected MANUAL OPERATION Manual Operation mode allows the operator to select one purge point continuously This is usually the case if a large volume of noncondensible gas is su...

Page 7: ...t will display the diagnostic code related to the occurrence which first put the APM into this mode exception 6666 will override 7777 Also see the troubleshooting guide on page 10 for detailed explana...

Page 8: ...d valves are required one for each enabled purge point These are not included with the APM The Hansen type HS8 solenoid valve having a 13mm port and a stainless steel piston is recommended Below is a...

Page 9: ...er diagnostic code 2222 flashes on the APM digital readout No purging of air will occur until foul gas pressure is restored OPERATION The foul gas may carry a certain amount of condensed refrigerant w...

Page 10: ...flooded evaporator is cooled down REASON 1 Suction temperature too high Check Verify the pressure at the purger suction line connection Action Connect to a lower temperature suction REASON 2 Restrict...

Page 11: ...ressure liquid available to maintain an adequate level in the flooded evaporator of the purger The purger will not purge air until this is corrected REASON 1 Liquid line solenoid valve B is not openin...

Page 12: ...to Piping Instructions in Section I of this bulletin Action Correct condenser and foul gas piping REASON 4 High side level sensor not detecting drop in liquid level due to oil Action Run recalibratio...

Page 13: ...QUID LINE SUCTION LINE 1 4 NPT 1 4 NPT SOCKET WELD SOCKET WELD SOCKET WELD VIEW ROTATED PIPE THREAD PIPE THREAD GAUGE VALVE GAUGE VALVE PURGER FRAME SHUT OFF VALVE VPM FOR CLARITY OPTIONAL VALVE PACKA...

Page 14: ...TIONAL VALVE PACKAGE VPMF The special construction for APMF AUTO PURGERs includes a filter dryer conditioning system for the foul gas and liquid line Water vapor as well as noncondensible gas may be p...

Page 15: ...20 1857 Temperature sensor 20 2303 High side level sensor 77 0796 Drainer and low side level sensor 77 0794 Solenoid coil kit 230V with DIN plug 70 1093 Solenoid coil kit 115V with DIN plug 70 1092 M...

Page 16: ...and the Nonelectrical AUTO PURGER NEAP Use the following descriptions to help select the best AUTO PURGER for your needs For additional assistance contact the factory AUTO PURGER AP This is the origin...

Reviews:

Related manuals for AUTO-PURGER M