Parker EME
Compax3 device description
192-120100 N16 C3I10T10 - December 2010
73
3.9.3.
Mounting and dimensions C3H
The devices must be mounted vertically on a level surface in the control cabinet.
(1): Electronics
(2): Head dissipator
H
H1
D
W
W1
C3H050V4
453mm
440mm
245mm
252mm
150mm
C3H090V4
668.6mm
630mm
312mm
257mm
150mm
C3H1xxV4
720mm
700mm
355mm
257mm
150mm
Mounting:
4 screws M6
During operation, the device radiates heat (power loss). Please provide for a
sufficient mounting distance below and above the device in order to ensure free
circulation of the cooling air. Please do also respect the recommended distances of
other devices. Make sure that the mounting plate is not exhibited to other
temperature influences than that of the devices mounted on this very plate.
If two or more devices are combined, the mounting distances are added.
Dimensions:
Ventilation: