45
PSUP30D6 Mains connection
Device type PSUP30
230V
400V
480V
Supply voltage
230VAC ±10%
50-60Hz
400VAC ±10%
50-60Hz
480VAC ±10%
50-60Hz
Rated voltage
3AC 230V
3AC 400V
3AC 480V
Input current
50Arms
50Arms
42Arms
Output voltage
325VDC ±10%
565VDC ±10%
680VDC ±10%
Output power
17kW
30kW
30kW
Pulse power (<5s)
34kW
60kW
60kW
Power dissipation
140W
140W
140W
Maximum fuse rating per
device (=short circuit rating)
2 circuit breakers in line are
required
Cable protection measure:
MCB (K characteristic) with a rating of 63A / 4xxVAC
(depending on the input voltage)
Recommendation: (ABB) S203U
-K63 (440VAC)
Device protection measure:
Circuit breakers 125A / 700VAC per supply leg in
accordance with UL category JFHR2
Requirement: Bussmann 170M1368 or 170M1568D
Only three-phase operation of the PSUP devices is permitted!
The PSUP30 mains module may only be operated with
mains filter
(see on
page 180)
Required mains filter for the PSUP30:
0.45 mH / 55 A
We offer the following mains filters:
LCG-0055-0.45 mH (WxDxH: 180 mm x 140 mm x 157 mm; 10 kg)
LCG-0055-0.45 mH-
UL (with UL approval) (WxDxH: 180
mm x 170 mm x
157 mm; 15 kg)
Dimensional drawing: LCG-0055-0.45 mH