background image

42

   

Reference & Installation Manual 

  

10.19 No Exit Delay Beeps and No Bell Squawk When Stay/Sleep Arming

Section 

[704]

: Arming/Disarming Options

Option 

[7]

 OFF = No Exit Delay Beeps and No Bell Squawk When Stay/Sleep Arming Disabled 

Option 

[7]

 ON = No Exit Delay Beeps and No Bell Squawk When Stay/Sleep Arming Enabled (default)

With this feature enabled, the control panel will prevent the bell or siren from squawking and the keypads from beeping during the 
exit delay, whenever a partition is Stay/Sleep armed. 

10.20 Exit Delay Termination

Section 

[700]

: Arming/Disarming Options

Option 

[6]

 OFF = Exit Delay Termination (Disabled) 

Option 

[6]

 ON = Exit Delay Termination Enabled (default)

When option [6] is enabled (ON), the panel will reduce the Exit Delay to 10 seconds when an Entry Delay zone is opened and 
closed during the Exit Delay.

Example: 15 seconds into a 45 second Exit Delay, an Entry Delay zone opens and closes. The remaining 30 seconds is reduced 
to 10 seconds. 

10.21 Fast Exit

When the system is already Stay or Sleep armed: This feature will allow you to exit and keep the system armed. Press and hold 
the 

[

OFF

]

 key for 3 seconds to start the exit delay. After the exit delay has elapsed, the system will switch to its previous arming 

mode.

Summary of Contents for Magellan MG5050 EN

Page 1: ...Reference Installation MG5000 V4 7 MG5050 V4 7 MG5050 EN V4 96 SP4000 V5 1 SP5500 V4 9 SP6000 V4 9 SP7000 V4 9...

Page 2: ...ng 32 Keyswitch Definitions 32 Keyswitch Options 32 Wireless Features 33 Wireless Transmitter Programming 33 Viewing the Wireless Transmitter Signal Strength 33 Supervision Options 33 RF Jamming Super...

Page 3: ...ble to reduce risk and or damage of burglary fire or other emergencies such other tools include but are not limited to insurance coverage fire prevention and extinguish devices and sprinkler systems W...

Page 4: ...ing to physically disconnect the control panel s power cables Press and hold the RESET switch for five seconds The STATUS LED will start flashing Within 2 seconds of this flashing press the reset swit...

Page 5: ...Idle SP65 1 2A Max 66mA Idle SP6000 1 7A Max 100mA Idle SP7000 1 7A Max 120mA Idle Aux power SP4000 450mA fuseless shutdown at 600mA SP65 500mA fuseless shutdown at 750mA SP5500 SP6000 SP7000 600mA ty...

Page 6: ...ialer grounds as shown in the PCB Layouts for each respective panel For UL installations the metallic enclosure must be grounded to the cold water pipe 2 4 AC Power Do not use any switch controlled ou...

Page 7: ...ross over the antennae as this may affect signal reception Paradox Memory Key PMC 4 PMC5 Antennas RX TX LED Flashes quickly when receiving or transmitting RF signals from wireless devices STATUS LED F...

Page 8: ...is shut down you must disconnect all loads from the output for at least 10 seconds before reconnecting any load back to the auxiliary output This equipment must be installed and maintained by qualifie...

Page 9: ...onnecting any load back to the auxiliary output This equipment must be installed and maintained by qualified service personnel only For UL and C UL warnings refer to the UL and C UL Warnings section a...

Page 10: ...o complete system shutdown Connection for Self Contained Bell Siren To provide maximum lightning protection we strongly recommend having separate earth connections for the dialer and zone ground termi...

Page 11: ...he sum of the current drawn from the BELL and AUX must be limited to 1 3A 40VA transformer strongly recommended Exceeding this limit will overload the panel power supply and lead to complete system sh...

Page 12: ...rrent drawn from the BELL and AUX must be limited to 1 3A 40VA transformer strongly recommended Exceeding this limit will overload the panel power supply and lead to complete system shutdown Connectio...

Page 13: ...dotted line represent the mounting location If you need specific dimensions contact Paradox Distributor Support For UL recommended installation for the MG5000 only place the PCB one notch lower than t...

Page 14: ...10 Reference Installation Manual SP5500 8x10 SP6000 11x11 SP7000 11x11...

Page 15: ...he control panel will re instate power to the BELL terminals during the next alarm When connecting sirens please verify correct polarity Connect the positive lead to the BELL terminal and the negative...

Page 16: ...motion detectors and door contacts are connected to the control panel s zone input terminals Figure 3 demonstrates single zone input terminal connections recognized by the panel Once connected the as...

Page 17: ...software oriented feature that enables two detection devices to be installed per hardwired input terminal Each detection device has its own zone displays its zone status on the keypad and sends its o...

Page 18: ...n 866 Figure 5 Fire Circuits 2 19 1 4 Wire and 2 Wire Installation For 4 wire installation program the Activation Event so that the smoke detectors can be reset by pressing the CLEAR ENTER keys for th...

Page 19: ...nal digit in a section the control panel will automatically save and advance to the next section Except sections 001 to 032 after entering the first three digits the control panel will switch to Featu...

Page 20: ...he Control Panel that you want to copy Make sure the write protect jumper of the Memory Key is on 3 Reapply AC and battery power 4 In Installer Programming Mode enter section 975 The keypad emits a co...

Page 21: ...ry Key onto the MEMKEY connector Partial view of control panel Prevents overwriting content of key Connection to module or panel Blue LED flashes only during transfer between the key and the PC Connec...

Page 22: ...LEEP Delete ARM Delete whole entry OFF Toggle numeric alphanumeric keys BYP Toggle lower case upper case MEM Special characters Label Sections 181 to 212 32 Zone Labels 341 to 356 16 PGM Labels 511 to...

Page 23: ...y once Press key twice Press key three times 1 A B G 2 D E Z 3 H Q I 4 K L M 5 N O 6 P R S 7 T U F 8 C Y W Greek Special Characters Catalogue 016 032 048 064 080 096 112 128 144 160 176 192 208 224 24...

Page 24: ...20 Reference Installation Manual Russian Special Characters Catalogue Russian Keypad Letter Assignment...

Page 25: ...ER INSTALLER CODE 398 new 4 or 6 digit Maintenance Code 5 4 System Master Code Default 1234 123456 The Installer Code can be used to program the System Master Code With the System Master Code a user c...

Page 26: ...The user code with this option enabled can arm assigned partitions but cannot disarm any partitions The type of arming is dependent on the other User Code Options selected Please note that with the A...

Page 27: ...te your path and once for the non path zone If you do not validate the non path zone the system will fall in alarm 6 3 Entry Exit with a Keypad When entering with a keypad the path zones will fall int...

Page 28: ...into section 710 Entry delay zones are commonly used at the entry exit points of the protected area i e front back door garage etc Using different entry delays is useful when for example one entry po...

Page 29: ...his will prevent the motion detector from causing an alarm when a user enters through the entry point to disarm the system See Zone Definition Status on page 28 for any exceptions 7 1 6 Follow Sleep F...

Page 30: ...ngs 7 1 14 Delayed Fire Silent Zones Sections 001 to 032 Zones 1 to 32 First Digits 14 When a Delayed Fire zone opens whether it is armed or disarmed the control panel will react as shown in Figure 10...

Page 31: ...t Digits 20 When a 24Hr Water zone opens whether it is armed or disarmed the control panel will immediately generate an alarm This alarm is defined by the alarm type configured in Zone Programming und...

Page 32: ...the Auto Zone Shutdown option enabled exceeds the number defined by the Auto Zone Shutdown Counter the control panel will no longer generate an alarm for that zone To program the Auto Zone Shutdown C...

Page 33: ...Selected Zone This feature reduces the possibility of false alarms When a zone with the Intellizone option opens the panel does not immediately generate an alarm First it triggers the Intellizone Dela...

Page 34: ...amper input By default it is a zone 7 9 Tamper Input on ZX8 ID C Panel 17 Section 706 General Zone Options 2 Option 6 OFF Zone C default Option 6 ON Tamper input Enabling this option will make the fir...

Page 35: ...n for three seconds then turn it to the OFF position 8 3 Keyswitch Options Each keyswitch zone can be programmed with one or more options 8 3 1 Stay Sleep Disarm Option Keyswitch On board hardwire con...

Page 36: ...t be used with any remote controls assigned to the control panel 9 3 1 Supervision Bypass Options Section 705 Arming Disarming Options Option 8 ON Generate Supervision Loss if detected on a Bypassed W...

Page 37: ...el 2 Program the buttons on the remote controls 9 6 1 Assigning a Remote Control to the Control Panel Sections 651 to 682 Remote Controls 1 to 32 respectively Remote controls are assigned to the panel...

Page 38: ...transmitters to send a status signal within a specified time to confirm their presence and functionality Option 1 OFF Keypad 1 Supervision Disabled Option 1 ON Keypad 1 Supervision Enabled default Op...

Page 39: ...to the control panel the signal strength of each repeater can be verified in sections 548 to 549 Section 548 is the viewer for repeater 1 and section 549 is the viewer for the repeater 2 Sometimes mov...

Page 40: ...y signals relevant to them Option 1 OFF Repeat Wireless Zone 1 Signals default Option 1 ON Repeat Wireless Zone 1 Signals Option 2 OFF Repeat Wireless Zone 2 Signals default Option 2 ON Repeat Wireles...

Page 41: ...22 Signals default Option 6 ON Repeat Wireless Zone 22 Signals Option 7 OFF Repeat Wireless Zone 23 Signals default Option 7 ON Repeat Wireless Zone 23 Signals Option 8 OFF Repeat Wireless Zone 24 Sig...

Page 42: ...nals Option 8 OFF Repeat Wireless 2 Way PGM 8 Signals default Option 8 ON Repeat Wireless 2 Way PGM 8 Signals Section 557 Repeater 1 and Section 567 Repeater 2 Wireless Repeater Options Enable or disa...

Page 43: ...rming Disarming Options Option 2 OFF Stay Arming Switches to Stay Force Arming Disabled Option 2 ON Stay Arming Switches to Stay Force Arming Enabled default With this feature enabled the control pane...

Page 44: ...everyday at 6 15PM enable Timed Auto arming for partition 2 by turning on option 1 in section 742 Then key in 18 15 into section 762 10 10 1 Auto Arm Timer Section 761 Partition 1 762 Partition 2 Sele...

Page 45: ...nt of time a user has to leave the protected area before the control panel arms the partition The exit delay applies to all zones in the selected partition When enabled the keypad will beep once every...

Page 46: ...Delay Termination Section 700 Arming Disarming Options Option 6 OFF Exit Delay Termination Disabled Option 6 ON Exit Delay Termination Enabled default When option 6 is enabled ON the panel will reduce...

Page 47: ...tion Options If a device has been tampered with i e the anti tamper switch has been set off the control panel can generate a trouble an alarm and or transmit a report code to the monitoring station Th...

Page 48: ...and 9 keys simultaneously on the keypad for 3 seconds will generate a silent or audible alarm as defined by option 6 Option 4 OFF Panic 1 is Silent default Option 4 ON Panic 1 is Audible Option 5 OFF...

Page 49: ...programmed amount of time in the partition Partial Arming A partition was Stay Sleep or Force armed or armed with Bypassed zones Section 861 Quick Arming A partition was armed using a One touch arming...

Page 50: ...pervision Lost The control panel has lost communication with a wireless zone Section 869 Wireless PGM Supervision Lost The control panel has lost communication with a wireless PGM Wireless PGM Tamper...

Page 51: ...hone number is programmed the control panel will never report to the backup telephone number Also see Delay Between Dialing Attempts on page 49 12 12 Personal Dialing Numbers Personal Dialing numbers...

Page 52: ...code from the Automatic Report Code List in the programming guide Alternatively report codes can be programmed using the Ademco Contact ID Report Codes in the programming guide 12 13 4 Event Call Dire...

Page 53: ...ect one of two Pulse Ratios Although most European countries use the 1 2 pulse ratio the 1 1 5 ratio may provide better results in some cases The same applies for North American countries If the 1 1 5...

Page 54: ...ed Report Delay determines the amount of time after an Disarming event that the control panel will wait before sending a report 12 24 Closing Delinquency Delay Section 719 000 Disabled 001 to 255 days...

Page 55: ...one or more conditions as defined by the TLM settings below These will be restored when the control panel detects the telephone line again Please note that when the dialer detects an incoming call th...

Page 56: ...the Plug in Voice Dialer when using a VDMP3 12 32 Personal Reporting Message Repetition Section 837 Communication Timers 000 to 255 times Max 10 Default 3 When using the Personal Reporting Format the...

Page 57: ...activate when the programmed PGM Deactivation Event occurs Instead of deactivating the PGM when a specific event occurs the PGM can deactivate after a programmed period elapses see PGM Delay on page 5...

Page 58: ...be verified in sections 321 to 336 Sometimes moving the PGM or control panel by a small amount will greatly increase the signal reception How Do I Assign PGMs to the Panel 1 Press the ENTER key 2 Ent...

Page 59: ...n 2 OFF Battery Charge Current 350mA default Option 2 ON Battery Charge Current 700mA 40VA transformer required 14 6 Partitioning Section 700 General Options Option 1 OFF Partitioning Disabled default...

Page 60: ...system s clock time for daylight savings changes At 2 00AM on the second Sunday of a full weekend in March the control panel will add one hour to the programmed time clock At 2 00 AM on the first Sund...

Page 61: ...g on AC failure When this option is enabled the panel will generate an audible trouble warning in the event of an AC failure 14 13 Display Entry Delay on LCD keypad K32LCD K32LCD Section 701 General S...

Page 62: ...ee rings 15 1 2 Number of Rings Section 901 000 disabled 001 to 015 rings Default 8 rings This value represents the number of rings the control panel will wait before picking up the line If the line i...

Page 63: ...upload the contents of the event buffer to the WinLoad software If communication is interrupted before completing transmission or if after two attempts communication is not established the system wil...

Page 64: ...y on the control panel 2 AC failure on control panel 3 Auxiliary overload on control panel 4 Wireless keypad AC failure 5 Wireless keypad battery failure 6 Wireless repeater AC failure 7 Wireless repe...

Page 65: ...ly Report Code 46 B Backup Battery 3 Battery specifications 2 Battery Charge Current 55 Battery Failure Report Code 46 Battery Backup 3 Beep On Exit Delay 41 Bell Cut Off Timer 43 Bell Output Connecti...

Page 66: ...Lockout Report Code 45 Panic Options 44 Keyswitch Arm Only 31 Definitions 31 Keyswitch Numbering 31 Maintained 31 Momentary 31 Options 31 Stay Instant Disarm 31 L Late to Close Report Code 45 Length o...

Page 67: ...45 Report Code Special Disarming Cancel Auto Arm 45 Remote Disarm 45 Report Code System Trouble AC Failure 46 Auxiliary Supply 46 Battery Failure 46 Bell Output Disconnected 46 Bell Output Overload 4...

Page 68: ...Live Display Mode 35 Wireless Keypad Options 34 35 Wireless Low Battery Report Code 46 Wireless Repeater Option 36 Wireless Repeater Programming 35 Wireless Serial Number Display 33 Wireless Transmitt...

Page 69: ...atisfaction Should you have any questions or comments please contact us For support please contact your local distributor or dial 1 800 791 1919 in North America You may also e mail us at distributors...

Reviews: