
44
Reference & Installation Manual
11.5
Tamper Bypass Options
Section
[705]
: Zone Options
Option
[5]
OFF = Tampers on bypassed zones will be ignored
Option
[5]
ON = Will generate a tamper if detected on a bypassed zone (default)
With option
[5]
off, the Tamper Recognition feature follows the zone bypass definition. This means the control panel will ignore
any tampers detected on a bypassed zone. With option
[5]
on, Tamper Recognition ignores the bypass definition. This means the
control panel will generate an incident as per Tamper Recognition settings if a tamper or wire fault occurs on a bypassed zone.
11.6
Tamper Supervision on the Bus Module
Section
[700]
: Supervision Options
Option
[7]
OFF = Tamper supervision disabled (default)
Option
[7]
ON = Tamper supervision enabled
When the control panel detects a tamper on a bus module, the control panel can generate an alarm or trouble, unless the Tamper
Supervision is disabled.
11.7
Keypad Panic Options
Section
[702]
: General Options
Option
[1]
OFF = Panic 1 Disabled (default)
Option
[1]
ON = Panic 1 Enabled
Pressing the
[1]
and
[3]
keys simultaneously on the keypad for 3 seconds will generate a silent or audible alarm as defined by
option
[4]
.
Option
[2]
OFF = Panic 2 Disabled (default)
Option
[2]
ON = Panic 2 Enabled
Pressing the
[4]
and
[6]
keys simultaneously on the keypad for 3 seconds will generate a silent or audible alarm as defined by
option
[5]
.
Option
[3]
OFF =
Panic 3 Disabled (default)
Option
[3]
ON =
Panic 3 Enabled
Pressing the
[7]
and
[9]
keys simultaneously on the keypad for 3 seconds will generate a silent or audible alarm as defined by
option
[6]
.
Option
[4]
OFF = Panic 1 is Silent (default)
Option
[4]
ON = Panic 1 is Audible
Option
[5]
OFF = Panic 2 is Silent (default)
Option
[5]
ON = Panic 2 is Audible
Option
[6]
OFF = Panic 3 is Silent (default)
Option
[6]
ON =
Panic 3 is Audible
Silent alarm
:
The control panel emits a confirmation beep and transmits the appropriate Panic report code if programmed in section
[863]
. The
control panel will not enable the keypad buzzers or the control panel’s
BELL
output (no audible alarm).
Audible alarm
:
Same as silent alarm, except the keypad buzzers and the
BELL
output will activate until a user cancels the alarm (disarms) with a
valid user access code or when the Bell Cut-Off Timer elapses (see
Bell Cut-Off Timer
on page 43).
Whether the system is partitioned or not, the control panel will report all panic alarms to partition 1.
11.8
Panic Lockout Timer
Section
[718]
When a panic alarm is activated, the control panel can ignore the disarm signal from a remote control for a specified period. This
prevents an aggressor from disarming the system by remote control during a panic situation. In section
[718]
enter a 3-digit value
(000 to 255, 000 = disabled) representing the number of seconds that the remote controls will be locked out of the system.
11.9
Flex-Instant Delay
Section
[720]
The Flex-Instant Delay is used to prevent false alarms when the premises is Stay/Sleep armed. In section
[720]
enter a 3-digit
value (000 to 255, 000 = disabled) representing the number of seconds that the panel will delay an alarm allowing you to disarm
the system (default 15 seconds).