- 17 -
will not enable the bell/siren output. Enter any valid
access code on the keypad to stop the buzzer.
Only keypads assigned to the same partition
as the “24
HR
” Buzzer zone will set off the
buzzer.
5.2.6 “24Hr” Burglary Zones
Sections [101] – [148]: First digit = 8
Whenever a
“24Hr” Burglary
zone opens, whether
the system is armed or disarmed, the control panel
will immediately generate an alarm. Detection
devices connected to hardwired-input terminals will
only cause the control panel to generate an alarm
after the
Input Speed
(see section 5.5) has elapsed.
5.2.7 Delayed “24Hr.” Fire Zone
Sections [101] – [148]: First digit = 9
The
Delayed “24Hr.” Fire Zone
definition described
in figure 5.4 is commonly used in residential homes
where a smoke detector often generates false
alarms (i.e. cigarette smoke, burning bread, etc.).
Note only keypads assigned to the same
partition as the Delayed “24
HR
” Fire zone
will activate the buzzer.
5.2.8 Standard “24Hr” Fire Zone
Sections [101] - [148]: First digit = A
For information on how to connect smoke detectors
to the control panel, refer to
Fire Circuits
in section
2.15. Whenever a
Standard “24Hr.” Fire Zone
opens, whether it is armed or disarmed, the control
panel will generate the following:
§
The control panel can send the appropriate
“Zone Alarm” report code (see section 9.2.5) to
the central station.
§
If a tamper/wiring fault occurs on a
Fire Zone
,
the control panel can send a “Global Fire Loop
Trouble Report (see section 9.2.11) to the
Central Station. A “Zone Fault Trouble” will also
appear in the keypad’s
Trouble Display
.
•
Fire alarms are always audible, regardless of
other settings. Fire alarms will generate an
intermittent bell/siren output signal as
demonstrated in
Figure 5-3
.
Figure 5.4 - Delayed 24Hr. Fire Zone
Delayed Fire Zone
Triggered
Activate bell/siren output & delay
report transmission for 30 seconds.
Yes
Yes
Any key on
keypad pressed
within 30
seconds?
Bell/siren silenced. Delay report
transmission an additional 90 sec.
Problem
corrected?
Latch alarm and transmit
report code as described
in section 5.2.8
END
Alarm Disabled
No
Has a 2nd
Delayed Fire
Zone opened in
30 sec.?
No
Yes
Yes
No
Has the zone
closed within
30 seconds?
Yes
No
5.3 Z
ONE
P
ARTITION
A
SSIGNMENT
Sections [101] - [148]: Second digit = 1-4
The control panel provides the option of partitioning
the security system into two, three, or four
completely independent systems. Therefore, each
zone must be assigned to one partition as described
in figure 5.1 on page 15. For more information on
Partitioning,
refer to section 12.6.
5.4 Z
ONE
O
PTIONS
Each zone can be programmed with one or more of
the options described below. Program the zone
options as described in figure 5.1 on page 15.