24
Inspecting the Installation
Inspect the installation to ensure appropriate sensor placement and a clean installation
area.
1. Verify sensor placement.
a. All pressure node and diffuser installations are positioned consistently.
b. Diffuser placement above floor and subfloor (as needed).
c. Zip ties and clips do not interfere with fans or bind or rub against surfaces.
2. Clear the installation area.
a. Remove all debris and tools from the data center floor.
b. Replace all floor tiles and close all cabinet doors.
c. Properly discard all packaging, snipped zip tie ends, etc.
PRESSURE NODE INSTALLATION MANUAL