Preparing to Install the Pressure Node Hardware
The SynapSense Field Engineer is responsible for completing these steps to confirm
installation readiness:
Assure the following steps are complete:
a. Required software is installed and configured.
b. Gateways are installed and powered on.
c. All products and tools necessary for installation are on site.
Verify the receipt of quantities and contents listed on packing/shipping list found in Box
1.
a. Place kits in front of each cabinet numbers on the kit bag (or as numbered on the printed MapSense
layout).
b. Verify install team has all necessary tools and additional materials to complete installation and site
is ready for installation.
For Pressure Nodes with MAC IDs not yet recorded or scanned, follow these steps:
a. Record the Pressure Node MAC IDs manually, or with a barcode scanner and upload into
MapSense.
b. Access the site layout from the MapSense application. Refer to the MapSense User Guide.
c. Add and configure Pressure Node objects and associated IDs in the data center floor plan.
Export the MapSense project .dlz file from MapSense for viewing in Web Console.
For cable assembly installations with subfloor sensors, determine where the subfloor
sensor routing will be located (rack and into the subfloor area).
Pressure Node Placement
Pressure Node and diffuser locations are either under server cabinets in overhead in air
plenums.