9
Required Software
The Pressure Node installation requires the installation of the following SynapSense
software:
•
Web Console™
•
MapSense™ (including optional Active Control™ software with MapSense project .dlz file exported to
the Web Console)
Installation of SynapSense software generally takes place prior to hardware installation.
This prevents redundancy of hardware verification activities. Refer to the SynapSense
Software, Web Console, and MapSense Installation and User Guides for more
information.
Required Tools and Materials
Table 3 lists the minimum tool and material requirements installers need to bring to the
job site.
Table 3 – Required Tools and Materials
Item
Description/Comments
Proper dress and shoes for performing work in a data center (including areas
Attire
inside the sub-floor and above ceiling tiles)
Ladder/Step Stool
To access all areas of the CRAC/CRAH units
Additional Parts
Spare ThermaNodes and batteries
Laptop
To configure settings (for example Modbus gateway)
Fasteners
Regular and plenum-rated zip ties, cable clips, and mounting brackets
7/32” Allen wrench, flashlight, diagonal cutters, utility knife, scissors, tile
Tools
pullers, thin blade screwdrivers, torque wrench, pliers, wire strippers, and
alcohol wipes
Multi-meter
Measures voltage in power sources
Label Maker
Create identification labels
Barcode scanner
Use to scan ThermaNode MAC IDs
•
A printed copy of this installation document
•
Web Console and MapSense User Guides
Documentation
•
Printed MapSense layout of the data center showing installation locations
Identification
Photo ID to present to data center security personnel
PRESSURE NODE INSTALLATION MANUAL