SMARTZONE G6 UPS USER MANUAL
64
Figure 54: Bypass Setting Page
Dry Contact Setting Pages
These two pages allow the user to set the meaning of the internal input and output dry
contact ports on the 3-phase UPS units only. These pages will not be available on the
5-10kVA Single-Phase UPS units. These pages have the same two banners across the
top of the page as described in the Status Menu page.
Input Dry Contact Setting Page
The main body of this page contains the settings for the four input dry contact ports
internal in the UPS.
Pressing the
left/right arrows on the “IN 01” line allows the user to select the meaning
(close, INV ON, INV OFF, BATT Fault, Generator, User Alarm3, User Alarm4,
Forbidden ECO, Force INV OFF, Input Switch, Bypass Switch, BATT Switch, BATT
Trip, BATT Ground, Thunder, or EPO) of the first input dry contact (between IN pins 1
and 2), default is Close. Close means there is nothing assigned to this input dry contact.
If “INV ON” is assigned to this contact, then a remote closure of this contact will cause
the inverter to turn ON.
Pressing the left/right arrows on the “IN 02” line allows the user to select the meaning of
the second input dry contact (between IN pins 3 and 4), default is Close. Close means
there is nothing assigned to this input dry contact. If “INV OFF” is assigned to this
contact, then a remote closure of this contact will cause the inverter to turn OFF.
Pressing the left/right arrows on the “IN 03” line allows the user to select the meaning of
the third input dry contact (between IN pins 5 and 6), default is Close. Close means
there is nothing assigned to this input dry contact.