SMARTZONE G6 UPS USER MANUAL
17
U10N12V / U10S12V
The 10kVA EU UPS unit has a terminal block for a hardwire connection on the input of
the UPS. This unit has three groups of outputs. Group 1 (hardwire connection) is the
main non-switchable output; this output should contain the critical loads. Group 2 (2x C-
13 with a 10A output breaker) are non-critical load switchable outlets. Group 3 (2x C-19
with a 16A output breaker) are switchable outlets; these outlets should contain non-
critical loads. During battery backup mode the Group 2 and Group 3 outlets may be
turned off earlier to conserve battery capacity for the Group 1 output.
Figure 10: European 10kVA Rear View (U10N12V / U10S12V)
5-10kVA 1-Phase UPS Physical Feature Call Out Table:
1. Mounting Bracket
6. EPO
11. Group 2 Outlets
2. Status LEDs & LCD
7. USB
12. Battery Terminals
3. Powe ON/OFF Button
8. RS232
13. Outlet Terminals
4. Intelligent Slot
9. BAT-T
14 Input Breaker
5. Maint. Bypass Signal
10. Group 2 Breaker