SMARTZONE G6 UPS USER MANUAL
56
Figure 47: System Settings Page (3-Phase UPS)
Parallel Setting Page
This page allows the user to set the Parallel System Configuration mode parameters of
the UPS. These functions are supported in the 3-phase UPS units only. This page is not
available on the 5-10kVA single-phase UPS units. This page has the same two banners
across the top of the page as described in the Status Menu page.
The main body of this page has the settings for the Parallel ID, the Number of Parallel
Units, and the number of the Redundant Units. A Parallel System Configuration may be
setup to have all units in parallel mode where total capacity of the system is the number
of units in the system times the capacity of one unit. A Parallel System Configuration
may alternately be setup in a parallel redundancy mode where total capacity of the
system is the number of units in the system minus the number of redundant units in the
system times the capacity of one unit.
Press the left/right arrow on the
“Parallel ID” line to select a number from 1 to 6 for the
parallel ID number of that UPS, default is 1. Each UPS in the Parallel Configuration
System must have as unique ID number.
Press the left/right arrow
on the “Parallel Basic Units” line to select the number of units
(2
– 6) in the Parallel System Configuration, the default number is 2.
Press the left/right arrow
on the (Parallel Redundancy Units” line to select the number of
units (0
– 5) in the Parallel System that are redundant units, the default number is 0.
When 0 is selected that means the Parallel System Configuration does not have
redundancy. When 1 to 5 are selected that means the system has 1 to 5 redundant
UPS units.