SMARTZONE G6 UPS USER MANUAL
55
Figure 46: Advanced Setting Menu Page
System Setting Pages
These pages allow the user to set the system parameters of the UPS. These pages
have the same two banners across the top of the page as described in the Status Menu
page.
System Setting Page 1
This page allows the user to select the working mode, set the system configuration and
select the input: output phase of the UPS. This page has the same two banners across
the top of the page as described in the Status Menu page.
The main body of this page has three lines, one for working mode, one for the system
configuration and one for input:output phases.
On the “Working Mode” line press on the left or right arrows to select Normal, Energy
Saving (ECO), Convert Frequency (CF) or Generator (Gen) working mode, default is
Normal mode.
On the “System Configuration” line press on the left or right arrows to select Single or
Parallel mode, default is Single mode. Parallel mode is an option only on the 3-Phase
UPS units. This line is not present on the 5-10kVA single-phase UPS units.
On the “Input:Output Phase” line press on the left or right arrows to select 3:3 or 3:1,
default is 3:3. Three Phase in and three phase out or three phase in and single phase
out is an option only on the 3-Phase UPS units. This line is not present on the 5-10kVA
single-phase UPS units.
After making all the necessary changes on this page, press the “Save Config” button to
save the changes.
Press the up and over arrow to return to the Advanced Setting Menu page.