Switching/Blind Actuator
7
Loads per output
Resistive load
3680 W
Capasitive load
max. 21uF at 16A
Motors (shutter or fan)
600W
Max. inrush current
80 A / 20 ms
Lamp Loads
Incandecent / Halogen load
2000 W
230 V halogen lamps
1800 W
LV halogen lamps with Tronic transformers
800 W
LV halogen lamps with inductive transformers
800 VA
Fluorescent lamp load (conventional) parallel-
corrected
2 x 58 W (7 μF), 3 x 36 W (4,5 μF), max. 120 W
(14 μF)
Fluorescent lamp load (conventional) not
corrected
14 x 58 W, 20 x 36 W, max. 1000 VA
Fluorescent lamp (EB - Electronic ballast)
3 x 36 W, 2 x 58 W, max. 120 W
Energy saving lamps
6 x 7 W, 4 x 11 W, 2 x 15 W, 2 x 20 W, 2 x 23 W