Switching/Blind Actuator
20
4.1.2.5
Staircase light timer with pre-warning Function and Parameters
Basic functionality: A "1" on the switching object switches the channel on for the duration of the
staircase light time. If another "1" is sent during this switch-on time then a further staircase light time
is added to the staircase light time which is already running. If a "0" is sent during this switch-on phase
then the channel switches off after a 30-second pre-warning. The light flickers briefly at the start of the
pre-warning period.
Name
Values
Description
Function
Switching
On/Off Delay
Pulse
Staircase light timer with
prewarning function
This function specifies the function type of the
channel. There are four type of selection function
for each channel.
Time base for staircase
time
1 sec.
10 sec.
30 sec.
1 min.
This parameter value is multiplied by the “factor
for staircase light time” parameter for defining
the staircase light time.
Factor for staircase light
time (1..255 x timebase)
*1…
5
…255] Defines the staircase light time together with the
“time base for staircase time”.
Staircase light time = basis * factor
Howmany pulse max. add
[1,
2
, …40+ This parameter value defines the maximum
number of pulses to be added to the actual
staircase light time. For ex. if its value is 10,
during staircase ligth time if more than 10 extra
pulses are added, only 10 extra pulses will
process.
Input logic
None
Lock
And
Override
None:
The channel only reacts to the switching
object in the way described at the beginning.
Lock:
If the linking object is set to "1" then no
staircase lighting can be started. The linking
object has no meaning for staircase lighting times
which are already running.
And:
If the linking object is set to "0" then no
staircase lighting can be started. For starting both
linking object and switching objects must be “1”.
The linking object has no meaning for staircase
lighting times which are already running.
Override:
If the linking object is set to "1" then
the channel is switched on regardless of the
switching object. Any waiting staircase lighting
times are deleted during an override.