Switching/Blind Actuator
14
4.1.2.2
Switching Function
Basic functionality: If the Function parameter is switching, then the channel is used for switching
function.
Name
Values
Description
Function
Switching
On/Off Delay
Pulse
Staircase light timer with prewarning
function
This function specifies the function type of the
channel. There are four type of selection function
for each channel.
Type of contact
Normally open
Normally close
This parameter sets the contact position of each
channel at startup (i.e when mains voltage applied
to the module)
Input logic
None
OR
AND
Lock
None:
The channel is not included any logic
operation.
Or:
If the switching object or the linking object is
“1” then the channel is “ON”. Both the switching
object and the linking object must be “0” at the
same time for channel “OFF” position.
And:
If the switching object and the linking object
are set to “1” then the channel is ON.
Lock:
If the linking object is set to “1” then the
channel is OFF then no switch-on is possible via the
switching object. If the linking object is set to “0”
then the contact is in the position according to the
switching object.
Participation in central
switching
No: in no central object
Yes: in all central object
Only in central continuous on
Only in central continuous off
Only in central switching
Only central switching and
continuous on
Only central switching and
continuous off
Central continuous on and central
continuous off
Defines which central objects the channel
responds to. The central objects have the following
priority:
If continuous ON is set to “1” then the channel is
switched on regardless of the other objects.
If continuous ON is set to “0” and continuous OFF
is set to “1” then the channel is switched off
regardless of the other objects.
Central switching does not take priority over the
switching object – the last command to be sent
applies.
The manual switches on the device take priority
over all bus commands.