99
16.5.13 Indoor/Outdoor Abnormal Communication (H90)
Malfunction Decision Conditions:
During operation of heating, the data received from outdoor unit in indoor unit signal transmission is checked
whether it is normal.
Malfunction Caused:
1 Faulty outdoor unit PCB (main).
2 Faulty indoor unit PCB (main).
3 Indoor-outdoor signal transmission error due to wrong wiring.
4 Indoor-outdoor signal transmission error due to breaking of wire in the connection wires between the indoor
and outdoor units.
5 Indoor-outdoor signal transmission error due to disturbed power supply waveform.
Abnormality Judgment:
Continue for 1 minute after operation.