Setting 2: When heating priority is not set by control panel:
When Solar Priority is set/not set by control panel:
1. 3 ways valve control:
o
3 ways valve switch to room side during heating heat-up interval, and switch to tank side during tank
heat-up interval. Both modes will switch alternatively. Tank mode is the Initial running mode of this heat
+ tank mode (heating no priority).
2. Heat pump operation control:
o
During heating heat-up interval
Follow normal heating operation
Under solar priority set condition:
Switch to tank heat-up interval and start counting tank heat-up timer when External Room Thermo
OFF
AND
solar 3WV OFF
AND
Tank temperature < THERMO ON TEMP (End Room Interval
Early)
OR
Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature <
THERMO ON TEMP
AND
solar 3WV OFF.
Under solar priority not set condition:
Switch to tank heat interval and start counting tank heat-up timer when External Room Thermo
OFF
AND
Tank < THERMO ON TEMP (End Room Interval)
OR
Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature <
THERMO ON TEMP.
* THERMO ON TEMP is defined Tank thermo ON/OFF condition below.
o
During tank heat-up interval
Heat pump tank target temperature = Tank set temperature or [60°C] whichever lower.
Heat pump Water Outlet set temperature is set to [63°C] during tank interval.
Initial Tank THERMO ON TEMP = heat pump tank target tempe [-8°C].
Tank thermo ON/OFF characteristic:
o
THERMO OFF TEMP:
1. THERMO OFF TEMP = Heat pump tank target tempe [0°C].
2. Tank temperature > THERMO OFF TEMP for continuous 10 seconds after heat pump off due
to water thermo, switch 3 ways valve to room side. End Tank heat-up interval and start count
heating heat-up interval.
3. Tank temperature > Tank set tempe [2°C] for continuous 10 seconds, switch 3 way
valve to room side. End Tank heat up interval and start count heating up interval.
o
THERMO ON TEMP:
1. THERMO ON TEMP = Heat pump tank target tempe [-8°C].
2. After heating heat-up interval, always detect tank temperature. Switch to next tank heat-up
interval when tank temperature < THERMO ON TEMP.
Summary of Contents for WH-SHF09F3E5
Page 19: ...19 4 2 Outdoor Unit Air inlet rear Air outlet Air inlet side ...
Page 32: ...32 10 1 2 Solar Printed Circuit Board Optional ...
Page 48: ...48 67 C 67 C 60 C 65 C 63 C 67 C 67 C ...
Page 49: ...49 60 C 60 C 65 C 65 C 72 C ...
Page 55: ...55 67 C 67 C 67 C 67 C ...
Page 56: ...56 67 C 67 C 60 C 60 C 55 C 75 C ...