16.5.25 Refrigeration Cycle Abnormality (F24)
Malfunction Decision Conditions:
1 During operation of heating, compressor frequency > Frated.
2 During operation of heating, running current: 0.65A < I < 1.65A.
3 During operation of heating, indoor refrigerant liquid temperature - water inlet temperature < 5°C.
Malfunction Caused:
1 Faulty water inlet or indoor refrigerant liquid temperature sensors.
2 3 way valve closed.
3 Refrigerant shortage (refrigerant leakage).
4 Clogged expansion valve or strainer.
5 Faulty outdoor unit PCB (main).
6 Poor compression of compressor.
Abnormality Judgment:
Continue 2 times in 20 minutes.