105
16.5.19 Compressor Rotation Failure (F14)
Malfunction Decision Conditions:
A compressor rotation failure is detected by checking the compressor running condition through the position
detection circuit.
Malfunction Caused:
1 Compressor terminal disconnect.
2 Faulty outdoor unit PCB (main).
3 Faulty
compressor.
Abnormality Judgment:
Continue 4 times in 20 minutes.
Summary of Contents for WH-SHF09F3E5
Page 19: ...19 4 2 Outdoor Unit Air inlet rear Air outlet Air inlet side ...
Page 32: ...32 10 1 2 Solar Printed Circuit Board Optional ...
Page 48: ...48 67 C 67 C 60 C 65 C 63 C 67 C 67 C ...
Page 49: ...49 60 C 60 C 65 C 65 C 72 C ...
Page 55: ...55 67 C 67 C 67 C 67 C ...
Page 56: ...56 67 C 67 C 60 C 60 C 55 C 75 C ...