Diagnosis display
Abnormality/Protection control
Abnormality judgement
Primary location to verify
F36
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
Outdoor air temperature sensor
(defective or disconnected)
F37
Indoor water inlet temperature sensor
abnormality
Continue for 5 sec.
Water inlet temperature sensor
(defective or disconnected)
F40
Outdoor discharge pipe temperature
sensor abnormality
Continue for 5 sec.
Outdoor discharge pipe temperature
sensor (defective or disconnected)
F41 PFC
control
4 times occurrence within 10
minutes
Voltage at PFC
F42
Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
Outdoor heat exchanger temperature
sensor (defective or disconnected)
F43
Outdoor defrost sensor abnormality
Continue for 5 sec.
Outdoor defrost sensor (defective or
disconnected)
F45
Indoor water outlet temperature sensor
abnormality
Continue for 5 sec.
Water outlet temperature sensor
(defective or disconnected)
F46
Outdoor Current Transformer open
circuit
—
Insufficient refrigerant
Outdoor PCB
Compressor low
F48
Outdoor EVA outlet temperature sensor
abnormality
Continue for 5 sec.
Outdoor EVA outlet temperature sensor
(defective or disconnected)
F49
Outdoor bypass outlet temperature
sensor abnormality
Continue for 5 sec.
Outdoor bypass outlet temperature
sensor (defective or disconnected)
F95
Cooling high pressure overload
protection
4 times occurrence in
20 minutes.
Outdoor high pressure sensor
Water pump or water leakage
Clogged expansion valve or strainer
Excess refrigerant
Outdoor PCB
Summary of Contents for WH-SHF09F3E5
Page 19: ...19 4 2 Outdoor Unit Air inlet rear Air outlet Air inlet side ...
Page 32: ...32 10 1 2 Solar Printed Circuit Board Optional ...
Page 48: ...48 67 C 67 C 60 C 65 C 63 C 67 C 67 C ...
Page 49: ...49 60 C 60 C 65 C 65 C 72 C ...
Page 55: ...55 67 C 67 C 67 C 67 C ...
Page 56: ...56 67 C 67 C 60 C 60 C 55 C 75 C ...