64
13.1.6 Low Pressure Protection Control
Purpose:
o
To protect the system operation.
o
Detection
period:
o
After compressor on for 5 minutes.
Detection
conditions:
o
When detection of Tem above 30°C.
o
Calculation of average evaporation temperature (Tem).
o
Use outdoor piping temperature sensor.
o
Tem use the value calculated for discharge temperature setting value.
After
detection:
o
Compressor stops restart again after 3 mins.
o
When abnormalities continuously generated 60 times within 480 minutes, system stops.
o
Protection operation is prohibited.
o
Error H42 will be displayed.
13.1.7 High Pressure Sensor Control
Purpose:
o
To protect the system operation.
Detection
period:
o
After compressor on for 1 minute.
Detection
conditions:
o
When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
After
detection:
o
When abnormality is detected continue 5 seconds, unit stop operation.
o
OFF/ON remote control LED will blink (H64 error occurs).
13.1.8 Outside Temperature Current Control
13.1.9 Extreme Low Temperature Control
Purpose:
- To improve the compressor reliability during cold start and after deice when running in extreme low outdoor
temperature -20°C.
Starting
condition:
o
Heating
operation
o
Outdoor air temperature < -10°C
o
Actual
frequency
≥
50Hz
o
Compressor discharge temperature < 20°C
When the above condition is fulfilled, this control is activated.
5Hz up every 30 sec. until it reaches the target frequency.
Cancellation
condition:
o
starting condition not fulfill.
o
Cancel the extreme low temperature control when compressor discharge sensor
≥
60°C
Summary of Contents for WH-MDC06E3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Page 11: ...11 4 1 1 Main Components ...
Page 13: ...13 ...
Page 14: ...14 ...
Page 15: ...15 4 1 3 Weekly Timer Setting ...
Page 16: ...16 4 1 4 Setting Up The Special Functions ...
Page 17: ...17 5 Dimensions 5 1 Mono Bloc Unit ...
Page 18: ...18 6 Refrigeration and Water Cycle Diagram ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram ...
Page 21: ...21 8 Wiring Connection Diagram ...
Page 22: ...22 ...
Page 23: ...23 9 Electronic Circuit Diagram ...
Page 24: ...24 ...
Page 25: ...25 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 26: ...26 10 1 2 Solar Printed Circuit Board Optional ...
Page 27: ...27 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 28: ...28 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 29: ...29 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 30: ...30 Main Components ...
Page 39: ...39 Cool Mode Operation Time Chart 12 1 4 Cool Tank Mode Operation ...
Page 41: ...41 ...
Page 42: ...42 ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 59: ...59 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 60: ...60 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 109: ...109 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge ...
Page 110: ...110 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 117: ...117 18 4 Hydraulic Pump Performance ...
Page 119: ...119 ...
Page 122: ...122 19 2 WH MDC06E3E5 WH MDC09E3E5 Water System ...