5 Three-way Valve shall be spring and electronic type, refer to “Field Supply Accessories” table for details.
Valve cable shall be (3 x min 0.5 mm
2
), of type designation 60245 IEC 57 or heavier, or similarly double
insulation sheathed cable.
* note: - Shall be CE marking compliance component.
- It shall be directed to heating mode when it is OFF.
- Maximum load for the valve is 9.8VA.
6 Room Thermostat cable shall be connected to “Room Thermostat”, refer to “Field Supply Accessories” table
for details. Room Thermostat cable must be (4 or 3 x min 0.5 mm
2
), double insulation layer of PVC-sheathed
or polychloroprene sheathed cable.
7 Tank OLP cable must be (2 x min 0.5 mm
2
), double insulation layer of PVC-sheathed or polychloroprene
sheathed cable.
* note: if such connection deemed NO necessary for tank OLP, please connect jumper between terminal
no. 13 and 14.
8 Tank Sensor shall be resistance type, please refer to Graph 4.1 for the characteristic and details of sensor.
Its cable shall be (2 x min 0.3 mm
2
), double insulation layer (with insulation strength of min 30V) of PVC-
sheathed or polychloroprene sheathed cable.
9 External Controller shall be connected to 1-pole switch with min 3.0mm contact gap. (connection refer to
Diagram 4.2). Its cable must be (2 x min 0.5 mm
2
), double insulation layer of PVC-sheathed or
polychloroprene sheathed cable.
* note: - When making such connection, kindly remove the jumper between terminal no. 17 and 18.
- Switch used shall be CE compliance component.
- Maximum operating current shall be less than 3A
rms
.
10 Must install Solar Connection PCB (optional) to Mono bloc unit when Solar Pump Station is utilized. Refer
Solar Connection PCB installation instruction for detail of installation.
11 Solar Three-way Valve cable shall be (3 x min 0.5 mm
2
), double insulation layer PVC-sheathed or
polychloroprene sheathed cable.
12 Solar Pump Station cable shall be (2 x min 0.5 mm
2
), of double insulation PVC-sheathed or polychloroprene
sheathed cable. Strongly recommended install with maximum length of 10 meter only.
Terminal screw
Tightening torque N•cm {kgf•cm}
M4 157~196
{16~20}
M5 196~245
{20~25}
11.4.1 Wire Stripping And Connecting Requirement
Summary of Contents for WH-MDC06E3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Page 11: ...11 4 1 1 Main Components ...
Page 13: ...13 ...
Page 14: ...14 ...
Page 15: ...15 4 1 3 Weekly Timer Setting ...
Page 16: ...16 4 1 4 Setting Up The Special Functions ...
Page 17: ...17 5 Dimensions 5 1 Mono Bloc Unit ...
Page 18: ...18 6 Refrigeration and Water Cycle Diagram ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram ...
Page 21: ...21 8 Wiring Connection Diagram ...
Page 22: ...22 ...
Page 23: ...23 9 Electronic Circuit Diagram ...
Page 24: ...24 ...
Page 25: ...25 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 26: ...26 10 1 2 Solar Printed Circuit Board Optional ...
Page 27: ...27 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 28: ...28 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 29: ...29 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 30: ...30 Main Components ...
Page 39: ...39 Cool Mode Operation Time Chart 12 1 4 Cool Tank Mode Operation ...
Page 41: ...41 ...
Page 42: ...42 ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 59: ...59 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 60: ...60 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 109: ...109 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge ...
Page 110: ...110 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 117: ...117 18 4 Hydraulic Pump Performance ...
Page 119: ...119 ...
Page 122: ...122 19 2 WH MDC06E3E5 WH MDC09E3E5 Water System ...