51
12.1.9 Fan
Motor
Operation
Fan motor is adjusted according to operation condition. It starts when compressor starts operation and it stops
30 seconds after compressor stops operation.
12.2 Water
Pump
12.2.1 Water Pump Control
Once the indoor unit is ON, the water pump will be ON immediately and no error judgement for 9 minutes.
However, during this 9 minutes operation, if there is any abnormality cause at outdoor or malfunction, the
compressor should be OFF immediately and restart delay after 3 minutes.
The system will start checking on the water flow level after operation start for 9 minutes. If water flow level is
detected low continuously for 10 secs, the water pump and compressor will be OFF permanently and OFF/ON
remote control LED will blink (H62 error occurs).
When error happen, the power has to be reset to clear the error.
If there is no error indication, the water pump shall be continuously running.
The water pump will remain ON when compressor OFF due to thermostat OFF setting is reached.
12.2.2 Water Pump Only Operation
Water pump only circulation can be set from the control panel SERVICE S/W when the operation is in Standby
Mode.
Press the SERVICE S/W for continuous 5sec to enter Service Mode.
In Service Mode, select Sr:02 and press SET S/W to start water pump only operation.
Water pump will stop operation when H62 is triggered.
Press the OFF/ON button to stop the water pump only operation.
Summary of Contents for WH-MDC06E3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Page 11: ...11 4 1 1 Main Components ...
Page 13: ...13 ...
Page 14: ...14 ...
Page 15: ...15 4 1 3 Weekly Timer Setting ...
Page 16: ...16 4 1 4 Setting Up The Special Functions ...
Page 17: ...17 5 Dimensions 5 1 Mono Bloc Unit ...
Page 18: ...18 6 Refrigeration and Water Cycle Diagram ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram ...
Page 21: ...21 8 Wiring Connection Diagram ...
Page 22: ...22 ...
Page 23: ...23 9 Electronic Circuit Diagram ...
Page 24: ...24 ...
Page 25: ...25 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 26: ...26 10 1 2 Solar Printed Circuit Board Optional ...
Page 27: ...27 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 28: ...28 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 29: ...29 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 30: ...30 Main Components ...
Page 39: ...39 Cool Mode Operation Time Chart 12 1 4 Cool Tank Mode Operation ...
Page 41: ...41 ...
Page 42: ...42 ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 59: ...59 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 60: ...60 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 109: ...109 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge ...
Page 110: ...110 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 117: ...117 18 4 Hydraulic Pump Performance ...
Page 119: ...119 ...
Page 122: ...122 19 2 WH MDC06E3E5 WH MDC09E3E5 Water System ...