53
12.6 Mono Bloc Unit Safety
12.6.1 Mono Bloc Unit Safety Control
1 When water pump is ON, the system will start checking flow switch status (ON/OFF).
2 If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds.
If the water inlet temperature not exceeds 80°C, the water pump shall be continuously running with normal
mode.
If the water inlet temperature exceeds 80°C for continuously 10 seconds, the water pump will be OFF
immediately.
3 After water pump OFF for more than 10 minutes, it will be ON back and the Mono bloc unit safety control
checking is restarted.
12.7 Auto
Restart
Control
When the power supply is cut off during the operation of Mono bloc unit, the compressor will re-operate after power
supply resumes.
12.8 Indication
Panel
LED Operation
Color Green
Light ON
Operation ON
Light OFF
Operation OFF
Note:
If Operation LED is blinking, there is an abnormality operation occurs.
Summary of Contents for WH-MDC06E3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Page 11: ...11 4 1 1 Main Components ...
Page 13: ...13 ...
Page 14: ...14 ...
Page 15: ...15 4 1 3 Weekly Timer Setting ...
Page 16: ...16 4 1 4 Setting Up The Special Functions ...
Page 17: ...17 5 Dimensions 5 1 Mono Bloc Unit ...
Page 18: ...18 6 Refrigeration and Water Cycle Diagram ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram ...
Page 21: ...21 8 Wiring Connection Diagram ...
Page 22: ...22 ...
Page 23: ...23 9 Electronic Circuit Diagram ...
Page 24: ...24 ...
Page 25: ...25 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 26: ...26 10 1 2 Solar Printed Circuit Board Optional ...
Page 27: ...27 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 28: ...28 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 29: ...29 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 30: ...30 Main Components ...
Page 39: ...39 Cool Mode Operation Time Chart 12 1 4 Cool Tank Mode Operation ...
Page 41: ...41 ...
Page 42: ...42 ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 59: ...59 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 60: ...60 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 109: ...109 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge ...
Page 110: ...110 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 117: ...117 18 4 Hydraulic Pump Performance ...
Page 119: ...119 ...
Page 122: ...122 19 2 WH MDC06E3E5 WH MDC09E3E5 Water System ...