Switch back 3 ways valve to room side, Heat pump and water pump turn OFF, IF
o
External Room Thermo ON back
OR
Under Solar Priority Set condition:
Tank temperature > Tank THERMO OFF TEMP. for continuous 3 minutes
OR
Solar Valve
ON
Under Solar Priority Not Set condition:
Tank temperature > Tank THERMO OFF TEMP for continuous 3 minutes
* THERMO ON and THERMO OFF point refer to case below.
Operation condition when 3 ways valve switch to tank side:
Tank water set temperature = tank set temperature or [51°C] whichever lower
Heat Pump Water Outlet set temperature is set to [55°C] during tank interval
Initial Tank THERMO ON TEMP = heat pump tank target tempe
[55°C]
Case 1:
o
THERMO OFF TEMP:
1.
THERMO OFF TEMP = Tank water set tempe
[0
°
C]
.
2.
Tank temperature > THERMO OFF TEMP for continuous 10 seconds after compressor off, switch
3 ways valve to room side.
o
Next THERMO ON TEMP:
1.
THERMO ON TEMP = Heat pump tank target tempe
[-2
°
C]
or
2.
If tank temperature < THERMO ON TEMP
AND
External Room Thermo OFF, switch to tank side.
Case 2:
o
Heat pump THERMO OFF TEMP:
1.
Heat pump THERMO OFF TEMP = 55°C +
[+2
°
C]
.
2.
Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat pump
OFF.
o
Next THERMO ON TEMP:
1.
THERMO ON TEMP = Water inlet when heat pump THERMO OFF +
[-3
°
C]
.
2.
If water outlet temperature < THERMO ON TEMP
AND
External Room Thermo OFF, heat pump ON.
Case 3:
o
Heat pump THERMO OFF TEMP:
1.
Water inlet temperature > 55°C for continuous 60 secs, heat pump OFF.
o
Next THERMO ON TEMP:
1.
THERMO ON TEMP = Water inlet temperature < 55°C.
2.
If water inlet temperature < THERMO ON TEMP AND External Room Thermo OFF, heat pump ON.
Case 4: (Only during solar priority is set condition)
o
When solar request ON, solar valve will ON and switch 3 ways valve to room side
o
THERMO ON TEMP:
1.
THERMO ON TEMP = Heat pump tank target tempe
[-2
°
C]
.
2.
If tank temperature < THERMO ON TEMP AND External Room Thermo OFF
AND
Solar 3WV OFF,
switch to tank side.
3 Backup Heater control:-
o
During External Room Thermo ON time, follow normal backup heater control operation
o
During External Room Thermo OFF time, Backup heater OFF
4
Booster heater control:
o
Booster heater On/Off follow normal operation.
* Under solar priority is set condition, when solar 3 way valve is ON, booster heater turn OFF.
Summary of Contents for WH-MDC06E3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Page 11: ...11 4 1 1 Main Components ...
Page 13: ...13 ...
Page 14: ...14 ...
Page 15: ...15 4 1 3 Weekly Timer Setting ...
Page 16: ...16 4 1 4 Setting Up The Special Functions ...
Page 17: ...17 5 Dimensions 5 1 Mono Bloc Unit ...
Page 18: ...18 6 Refrigeration and Water Cycle Diagram ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram ...
Page 21: ...21 8 Wiring Connection Diagram ...
Page 22: ...22 ...
Page 23: ...23 9 Electronic Circuit Diagram ...
Page 24: ...24 ...
Page 25: ...25 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 26: ...26 10 1 2 Solar Printed Circuit Board Optional ...
Page 27: ...27 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 28: ...28 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 29: ...29 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 30: ...30 Main Components ...
Page 39: ...39 Cool Mode Operation Time Chart 12 1 4 Cool Tank Mode Operation ...
Page 41: ...41 ...
Page 42: ...42 ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 59: ...59 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 60: ...60 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 109: ...109 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge ...
Page 110: ...110 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 117: ...117 18 4 Hydraulic Pump Performance ...
Page 119: ...119 ...
Page 122: ...122 19 2 WH MDC06E3E5 WH MDC09E3E5 Water System ...