13.1.10 Crank Case Heater Control
Purpose:
- For compressor protection during low outdoor ambient operation (during heating low temperature operation).
Control
content:
a. Trigger heater START condition
o
When the outdoor air temperature is 4°C or below, and discharge temperature is 12°C or below.
b. Resetting heater STOP condition
1.
when the outdoor air temperature exceeds entry condition 6°C.
2.
when the discharge temperature exceeds entry condition 19°C.
13.2 Protection Control for Heating Operation
13.2.1 Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid
compressor overloading.
13.2.2 Deice
Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor
stop.
13.2.3 Heat-exchanger (hot water coil) protection control
Backup heater ON condition:-
o
water inlet temperature < 18°C
AND
o
outdoor ambient temperature < 10°C
Backup heater OFF condition:-
o
water inlet temperature > 20°C
OR
o
outdoor ambient temperature > 13°C
However this control will take place 29 minutes after compressor restart.
Summary of Contents for WH-MDC06E3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Page 11: ...11 4 1 1 Main Components ...
Page 13: ...13 ...
Page 14: ...14 ...
Page 15: ...15 4 1 3 Weekly Timer Setting ...
Page 16: ...16 4 1 4 Setting Up The Special Functions ...
Page 17: ...17 5 Dimensions 5 1 Mono Bloc Unit ...
Page 18: ...18 6 Refrigeration and Water Cycle Diagram ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram ...
Page 21: ...21 8 Wiring Connection Diagram ...
Page 22: ...22 ...
Page 23: ...23 9 Electronic Circuit Diagram ...
Page 24: ...24 ...
Page 25: ...25 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 26: ...26 10 1 2 Solar Printed Circuit Board Optional ...
Page 27: ...27 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 28: ...28 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 29: ...29 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 30: ...30 Main Components ...
Page 39: ...39 Cool Mode Operation Time Chart 12 1 4 Cool Tank Mode Operation ...
Page 41: ...41 ...
Page 42: ...42 ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 59: ...59 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 60: ...60 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 109: ...109 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge ...
Page 110: ...110 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 117: ...117 18 4 Hydraulic Pump Performance ...
Page 119: ...119 ...
Page 122: ...122 19 2 WH MDC06E3E5 WH MDC09E3E5 Water System ...