Backup and Emergency Operation
PACD011001C2
558
Special Service Mode UM Combination “MA1R Series” Using R-407C
1.
Backup and Emergency Operation
1.1
Backup and Emergency Operation
1.1.1
Backup Operation
:
When a constant speed type compressor malfunctions due to OC actuation, if you restart operation by
remote controller after the unit stops, you can continue to operate the system without the faulty constant
speed type compressor.
The system can run by backup operation for up to 3 hours of total indoor unit operating time. When 3 hours
is exceeded and the malfunction still remains, the system once again stops due to malfunction. If the
malfunction returns to normal, the system continues to operate as is.
Backup Operation
Control Flow
After the system briefly stops due malfunction in order to call attention to the problem, backup operation is
started by remote controller.
For the reason described above, after about 3 hours of backup operation, the system again carries out
malfunction detection, and the system once again stops due to malfunction if an error is detected.
Note:
1. < For 2-compressor system >
„
When the STD compressor OC operates, the operation continues using only the inverter compressor
based on remote control reset. (for 3 hours only)
< For 3-compressor system >
„
When OC operates again immediately after a backup operation (within 5 minutes after STD compressor
startup), STD1 and STD2 are switched and operation is retried.
„
If OC activates again, only the inverter compressor is used for the operation.
„
(In any case, the backup operation ends after 3 hours.)
„
The compressor in which OC is activated is prohibited to operate until power reset is conducted for a
restart.
Malfunction occurs.
(MF168)
Malfunction detection
System stops due to malfunction.
Backup operation starts.
Operates without faulty constant
speed (STD) compressor. (Note 1)
Returns to normal operation.
No malfunction
3 hours elapse.
Remote controller reset
Malfunction
occurs again.
Summary of Contents for Urban Multi MX1R Series
Page 13: ...PACD011001C2 xii Table of Contents ...
Page 23: ...PACD011001C2 2 Urban Multi MX1 ME1 Series Using R 22 ...
Page 125: ...Test Operation PACD011001C2 104 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 155: ...Test Operation PACD011001C2 134 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 239: ...PACD011001C2 218 Urban Multi MX1R ME1R Series Using R 407C ...
Page 245: ...Outline PACD011001C2 224 General Information Urban Multi MX1R ME1R Series Using R 407C ...
Page 293: ...Function PACD011001C2 272 Function Urban Multi MX1R ME1R Series Using R 407C ...
Page 343: ...Test Operation PACD011001C2 322 Test Operation Urban Multi MX1R ME1R Series Using R 407C ...
Page 427: ...PACD011001C2 406 UM Combination MA1R Series Using R 407C ...
Page 433: ...Product Outline PACD011001C2 412 General Information UM Combination MA1R Series Using R 407C ...
Page 501: ...Test Operation PACD011001C2 480 Test Operation UM Combination MA1R Series Using R 407C ...
Page 586: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 565 CZ 100 160HR1HE ...
Page 590: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 569 CZ 100 160HR1HP ...
Page 592: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 571 PA 24 26 28 30MA1XPK ...
Page 594: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 573 CS 40 50 80 125LMHPP ...
Page 596: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 575 2 3 Corner Type CS 25 32 40 63DM1HPK ...
Page 598: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 577 CS 80 100 125FMHPP ...
Page 600: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 579 CS 200 250EMHPK ...
Page 601: ...Wiring Diagrams Indoor Unit PACD011001C2 580 Appendix 2 6 Ceiling Type CS 32 63 100TMJPL ...
Page 604: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 583 2 9 Small Duct Type CS 20 25NM1HPP ...