PACD011001C2
Function
Function Urban Multi “MX1R, ME1R Series” Using R-407C
233
1.1.5
Function of Thermistors and Pressure Sensors
Outdoor unit
CU-8·10MX1SPP
Receiver
Filter
Electronic
expansion
valve
Solenoid
valve
Solenoid
valve
Filter
Fan
Fan
Heat exchanger
4-way changeover valve
Capillary
tube
Capillary tube
Pressure
sensor
(High
pressure)
Solenoid
valve
Oil
separator
Oil
separator
Filter
Filter
High
pressure
switch
Inverter
comp-
ressor
Capillary
tube
Capillary
tube
Standard
comp-
ressor
High pressure
switch
Accumulator
Pressure sensor
(Low pressure)
Gauge port
This piping diagram shows the inverter compressor on the left side,
but it is located on the right side on an actual machine.
Stop valve
(With service port on field piping side)
High pressure sensor (SENPH)
When heating:
Used for compressor
capacity control by sensing
high pressure.
When cooling:
Carries out heat exchange
control during low outdoor
air cooling.
Outdoor temperature
thermistor (R1T)
(When heating)
1
Used as the function for
defrost IN conditions.
1
OFF by thermostat when
temperature becomes 27
C or higher
Coil temperature thermistor (R2T)
(When cooling)
Not used for anything.
(When heating)
Used together with outdoor
temperature as the function for
defrost IN conditions.
Oil temperature thermistor (R5T)
(8, 10 HP only)
(When heating)
1
Alters the desired superheat
degree (SH) to prevent wet
operation.
(When defrosting)
1
Controls upper limit frequency
to improve dilution of oil.
Discharge pipe temperature
thermistor
R3-1T (Inverter compressor)
R3-2T (Standard compressor)
Used for compressor discharge
temperature safety.
Suction pipe temperature
thermistor (R4T)
Used for superheat
control of electronic
expansion valve when
heating.
Low pressure sensor (SENPL)
When heating:
Used for compressor capacity control and low
pressure safety control by sensing high pressure.
When cooling:
Used for overheating control and low pressure
safety control.
(M008)
Summary of Contents for Urban Multi MX1R Series
Page 13: ...PACD011001C2 xii Table of Contents ...
Page 23: ...PACD011001C2 2 Urban Multi MX1 ME1 Series Using R 22 ...
Page 125: ...Test Operation PACD011001C2 104 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 155: ...Test Operation PACD011001C2 134 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 239: ...PACD011001C2 218 Urban Multi MX1R ME1R Series Using R 407C ...
Page 245: ...Outline PACD011001C2 224 General Information Urban Multi MX1R ME1R Series Using R 407C ...
Page 293: ...Function PACD011001C2 272 Function Urban Multi MX1R ME1R Series Using R 407C ...
Page 343: ...Test Operation PACD011001C2 322 Test Operation Urban Multi MX1R ME1R Series Using R 407C ...
Page 427: ...PACD011001C2 406 UM Combination MA1R Series Using R 407C ...
Page 433: ...Product Outline PACD011001C2 412 General Information UM Combination MA1R Series Using R 407C ...
Page 501: ...Test Operation PACD011001C2 480 Test Operation UM Combination MA1R Series Using R 407C ...
Page 586: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 565 CZ 100 160HR1HE ...
Page 590: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 569 CZ 100 160HR1HP ...
Page 592: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 571 PA 24 26 28 30MA1XPK ...
Page 594: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 573 CS 40 50 80 125LMHPP ...
Page 596: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 575 2 3 Corner Type CS 25 32 40 63DM1HPK ...
Page 598: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 577 CS 80 100 125FMHPP ...
Page 600: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 579 CS 200 250EMHPK ...
Page 601: ...Wiring Diagrams Indoor Unit PACD011001C2 580 Appendix 2 6 Ceiling Type CS 32 63 100TMJPL ...
Page 604: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 583 2 9 Small Duct Type CS 20 25NM1HPP ...