PACD011001C2
Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting Urban Multi “MX1, ME1 Series” Using R-22
215
8.3
Display “Under Host Computer Integrate Control” Blinks (Repeats Double
Blink)
Remote Controller
Display
“under host computer integrated control” (Repeats double blink)
Supposed Causes
„
Central control address (group No.) is not set for indoor unit.
„
Improper address setting
„
Improper wiring of transmission wiring
Troubleshooting
(VF082)
Is the switch
for setting each address set
correctly?
Is
the transmission
wiring disconnected or wired
incorrectly?
Fix the wiring correctly.
Replace the PC board of the unified
ON/OFF controller.
Set by remote controller the central
control address for all indoor units
connected to the central control line.
YES
YES
NO
Set the switch for setting each address
correctly and simultaneously reset the
power supply for all optional controllers
for centralised control.
NO
NO
YES
Is the central
control address (group No.)
set for the indoor
unit?
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for Urban Multi MX1R Series
Page 13: ...PACD011001C2 xii Table of Contents ...
Page 23: ...PACD011001C2 2 Urban Multi MX1 ME1 Series Using R 22 ...
Page 125: ...Test Operation PACD011001C2 104 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 155: ...Test Operation PACD011001C2 134 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 239: ...PACD011001C2 218 Urban Multi MX1R ME1R Series Using R 407C ...
Page 245: ...Outline PACD011001C2 224 General Information Urban Multi MX1R ME1R Series Using R 407C ...
Page 293: ...Function PACD011001C2 272 Function Urban Multi MX1R ME1R Series Using R 407C ...
Page 343: ...Test Operation PACD011001C2 322 Test Operation Urban Multi MX1R ME1R Series Using R 407C ...
Page 427: ...PACD011001C2 406 UM Combination MA1R Series Using R 407C ...
Page 433: ...Product Outline PACD011001C2 412 General Information UM Combination MA1R Series Using R 407C ...
Page 501: ...Test Operation PACD011001C2 480 Test Operation UM Combination MA1R Series Using R 407C ...
Page 586: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 565 CZ 100 160HR1HE ...
Page 590: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 569 CZ 100 160HR1HP ...
Page 592: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 571 PA 24 26 28 30MA1XPK ...
Page 594: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 573 CS 40 50 80 125LMHPP ...
Page 596: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 575 2 3 Corner Type CS 25 32 40 63DM1HPK ...
Page 598: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 577 CS 80 100 125FMHPP ...
Page 600: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 579 CS 200 250EMHPK ...
Page 601: ...Wiring Diagrams Indoor Unit PACD011001C2 580 Appendix 2 6 Ceiling Type CS 32 63 100TMJPL ...
Page 604: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 583 2 9 Small Duct Type CS 20 25NM1HPP ...