PACD011001C2
Troubleshooting (OP: Schedule Timer)
Troubleshooting UM Combination “MA1R Series” Using R-407C
551
7.4
Improper Combination of Optional Controllers for Centralised Control
Remote Controller
Display
MA
Supposed Causes
„
Improper combination of optional controllers for centralised control
„
More than one master controller is connected.
„
Defect of PC board of optional controllers for centralised control
Troubleshooting
Disconnect the schedule timer's
individual / combined connector
and reset the power supply for all
optional controllers for centralised
control simultaneously.
Arrange so that the connector for
setting master control is connected
to one controller for centralized
control and reset the power supply
for all optional controllers for
centralised control simultaneously.
Disconnect the connector for
setting master control from the
master controller, connect to
another optional controller for
centralised control and
simultaneously reset all optional
controllers for centralised control
again. The controller connected by
the connector for setting master
control when the malfunction is
cleared is defective and must be
replaced.
Reset the power supply for all
optional controllers for
centralized control
simultaneously.
YES
YES
NO
Is the schedule
timer connected?
Are
there two or
more optional controllers
for centralized control connected
with the connector for
setting master
control?
YES
Is the schedule
timer's individual/combined
connector connected?
NO
NO
Cannot be used in combination
with a "BMS interface adaptor for
individual and unified control, for
unified group". Remove them and
reset the power supply for all
optional controllers for centralised
control simultaneously.
YES
Is the "BMS
interface adaptor for
individual and unified control,
for unified group"
connected?
NO
Schedule timer and data station
cannot be used in combination.
Disconnect either the schedule
timer or data station and reset the
power supply for all optional
controllers for centralised control
simultaneously.
YES
Is a data station connected?
NO
Schedule timer and parallel
interface cannot be used in
combination. Disconnect either the
schedule timer or parallel interface
and reset the power supply for all
optional controllers for centralised
control simultaneously.
YES
Is a parallel interface
connected?
NO
If the malfunction is still not cleared:
(VF077)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for Urban Multi MX1R Series
Page 13: ...PACD011001C2 xii Table of Contents ...
Page 23: ...PACD011001C2 2 Urban Multi MX1 ME1 Series Using R 22 ...
Page 125: ...Test Operation PACD011001C2 104 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 155: ...Test Operation PACD011001C2 134 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 239: ...PACD011001C2 218 Urban Multi MX1R ME1R Series Using R 407C ...
Page 245: ...Outline PACD011001C2 224 General Information Urban Multi MX1R ME1R Series Using R 407C ...
Page 293: ...Function PACD011001C2 272 Function Urban Multi MX1R ME1R Series Using R 407C ...
Page 343: ...Test Operation PACD011001C2 322 Test Operation Urban Multi MX1R ME1R Series Using R 407C ...
Page 427: ...PACD011001C2 406 UM Combination MA1R Series Using R 407C ...
Page 433: ...Product Outline PACD011001C2 412 General Information UM Combination MA1R Series Using R 407C ...
Page 501: ...Test Operation PACD011001C2 480 Test Operation UM Combination MA1R Series Using R 407C ...
Page 586: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 565 CZ 100 160HR1HE ...
Page 590: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 569 CZ 100 160HR1HP ...
Page 592: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 571 PA 24 26 28 30MA1XPK ...
Page 594: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 573 CS 40 50 80 125LMHPP ...
Page 596: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 575 2 3 Corner Type CS 25 32 40 63DM1HPK ...
Page 598: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 577 CS 80 100 125FMHPP ...
Page 600: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 579 CS 200 250EMHPK ...
Page 601: ...Wiring Diagrams Indoor Unit PACD011001C2 580 Appendix 2 6 Ceiling Type CS 32 63 100TMJPL ...
Page 604: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 583 2 9 Small Duct Type CS 20 25NM1HPP ...