Troubleshooting by Remote Controller
PACD011001C2
496
Troubleshooting UM Combination “MA1R Series” Using R-407C
2.6
Remote Controller Self-Diagnosis Function
(Display of Malfunction Code)
The remote controller switches are equipped with a self diagnosis function so that more appropriate
maintenance can be carried out. If a malfunction occurs during operation, the operation lamp, malfunction
code and display of malfunctioning unit No. let you know the contents and location of the malfunction.
When there is a stop due to malfunction, the contents of the malfunction given below can be diagnosed by
a combination of operation lamp, INSPECTION display of the liquid crystal display and display of
malfunction code. It also lets you know the unit No. during group control.
Malfunction Code List
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Refered
Indoor Unit
A0
9
9
9
Error of external protection device
A1
9
9
9
PC board defect
A1
8
7
9
PC board defect
A3
9
9
9
Malfunction of drain level control system (33H)
A6
9
9
9
Fan motor (M1F) lock, Overload
A7
8
7
9
Malfunction of swing flap motor (M1S)
A9
9
9
9
Malfunction of moving part of electronic expansion valve
(Y1E)
AF
8
7
9
Drain level above limit
AH
9
9
9
Malfunction of air filter maintenance
—
AJ
9
9
9
Malfunction of capacity determination device
C4
9
9
9
Malfunction of thermistor (R2T) for liquid pipe (loose
connection, disconnection, short circuit, failure)
C5
9
9
9
Malfunction of thermistor (R3T) for gas pipes (loose
connection, disconnection, short circuit, failure)
C9
9
9
9
Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
CJ
8
8
8
Malfunction of thermostat sensor in remote controller
Outdoor
Unit
E0
9
9
9
Actuation of safety device
E1
9
9
9
PC board defect
E1
8
7
9
PC board defect
E3
9
9
9
Actuation of high pressure switch
E4
9
9
9
Actuation of low pressure switch
E9
9
9
9
Malfunction of moving part of electronic expansion valve
(Y1E)
F3
9
9
9
Abnormal discharge pipe temperature
H3
8
7
9
High pressure switch failure
—
H4
9
9
9
Actuation of low pressure switch
—
H9
9
9
9
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
H9
8
7
9
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
J1
9
9
9
Malfunction of pressure sensor
—
J3
9
9
9
Malfunction of discharge pipe thermistor (R3T) (loose
connection, disconnection, short circuit, failure)
J3
8
7
9
Malfunction of discharge pipe thermistor (R3T) (loose
connection, disconnection, short circuit, failure)
J5
9
9
9
Malfunction of thermistor (R4T) for suction pipe (loose
connection, disconnection, short circuit, failure)
Summary of Contents for Urban Multi MX1R Series
Page 13: ...PACD011001C2 xii Table of Contents ...
Page 23: ...PACD011001C2 2 Urban Multi MX1 ME1 Series Using R 22 ...
Page 125: ...Test Operation PACD011001C2 104 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 155: ...Test Operation PACD011001C2 134 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 239: ...PACD011001C2 218 Urban Multi MX1R ME1R Series Using R 407C ...
Page 245: ...Outline PACD011001C2 224 General Information Urban Multi MX1R ME1R Series Using R 407C ...
Page 293: ...Function PACD011001C2 272 Function Urban Multi MX1R ME1R Series Using R 407C ...
Page 343: ...Test Operation PACD011001C2 322 Test Operation Urban Multi MX1R ME1R Series Using R 407C ...
Page 427: ...PACD011001C2 406 UM Combination MA1R Series Using R 407C ...
Page 433: ...Product Outline PACD011001C2 412 General Information UM Combination MA1R Series Using R 407C ...
Page 501: ...Test Operation PACD011001C2 480 Test Operation UM Combination MA1R Series Using R 407C ...
Page 586: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 565 CZ 100 160HR1HE ...
Page 590: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 569 CZ 100 160HR1HP ...
Page 592: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 571 PA 24 26 28 30MA1XPK ...
Page 594: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 573 CS 40 50 80 125LMHPP ...
Page 596: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 575 2 3 Corner Type CS 25 32 40 63DM1HPK ...
Page 598: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 577 CS 80 100 125FMHPP ...
Page 600: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 579 CS 200 250EMHPK ...
Page 601: ...Wiring Diagrams Indoor Unit PACD011001C2 580 Appendix 2 6 Ceiling Type CS 32 63 100TMJPL ...
Page 604: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 583 2 9 Small Duct Type CS 20 25NM1HPP ...